Series-AVLV

Air Velocity Transmitter ± 1% Accuracy, Configurable Outputs, BACnet/Modbus

  • Sensing elements have been coated with an engineered conformal coating to ensure durability and longevity
  • Field selectable ranges can be quickly configured without power to the unit
Series-AVLV
From C$ 443.85
Air Velocity Transmitter ± 1% Accuracy, Configurable Outputs, BACnet/Modbus Series-AVLV Series-AVLV
loading all models
Product Overview
  • Air Velocity, Max 400 FPM
  • Air Velocity, Min 20 FPM
  • Air Velocity Note 100, 200, 300, 400 FPM (0.5, 1, 1.5, 2 m/s); Field selectable
  • Applications Clean Rooms, Pharmaceutical
  • Baud Rate N/A
  • Device Load 1/8 Unit
  • Enclosure Ratings IP66, NEMA Type 4X
  • Load Resistance Current output: 0 to 1100 Ω max; Voltage Output: 1 kΩ min
  • Materials, Wetted Consult Factory
  • Media Compatibility Clean dry air / inert gas, Inert / non-reactive gases, Clean Dry Air, Helium, Nitrogen, Non-Corrosive Dry Gases
  • Mounting Orientation Sensor Tip Parallel to Flow
  • Operating Temperature, Max 122 °F
  • Operating Temperature, Min 32 °F
  • Output Detail 4 to 20 mA; 0 to 5 Vdc, 0 to 10 Vdc
  • Output Signal Current, Voltage
  • Power Consumption 60 mA + Output Current
  • Relative Humidity 5 to 95% RH Non-Condensing
  • Response Time 4 s
  • Response Time Note 4 s, typical; 1 s at constant temperature
  • Series ID Series-AVLV
  • Supply Power Type AC/DC
  • Supply Voltage 19 to 30 Vdc/Vac
  • Weight 6 oz
  • Wire Gauge 26 to 16 AWG
  • Zero Setting Adjustable Range Digital Push Buttons

Supported Applications

The Dwyer Series AVLV Low Air Velocity Transmitter measures air velocity or volumetric flow in imperial or metric units. The series is designed for quality-intensive environments, such as the pharmaceutical industry, where lower ranges and high accuracy are required. It operates with clean air and non-combustible, compatible gases.

Operating Conditions & Performance

The Series AVLV functions within an ambient temperature range of 32 to 122°F (0 to 50°C) and a humidity rating of 5 to 95% RH, non-condensing. Accuracy is available in two classes: ± (2% of reading + offset) or ± (1% of reading + offset), with the specific offset dependent on the selected velocity range.

  • Velocity Ranges: Field selectable full-scale ranges include 100, 200, 300, and 400 FPM (0.5, 1.0, 1.5, 2.0 m/s). The accuracy chart defines performance for velocity spans starting at 20 to 100 FPM (0.15 to 0.5 m/s) up through 20 to 400 FPM (0.15 to 2.0 m/s).
  • Accuracy Offsets: For the 20 to 100/200 FPM ranges, the offset is ± 0.04 m/s [7.9 FPM]. The 20 to 300 FPM range lists an offset of ± 0.05 m/s [9.8 FPM], and the 20 to 400 FPM range lists ± 0.06 m/s [11.8 FPM].
  • Response Time: Typical response time is 4 s (90%); it reduces to 1 s at constant temperature.
  • Enclosure Rating: NEMA 4X (IP66).

Configuration Options

The series supports simultaneous current and voltage outputs, configurable via local DIP switches. Models are available with or without an optional integral display.

  • Output Signals: 4-20 mA, 0-5 VDC, or 0-10 VDC (configurable). Communication options include BACnet MS/TP or Modbus® RTU/ASCII via RS-485.
  • Power Supply: 24 VDC ±20% or 24 VAC ±20%. Current consumption is 60 mA max.
  • Load Resistance: Current output supports 0 to 1100 Ω max; voltage output requires a minimum load resistance of 1 kΩ.
  • Housing & Mounting: Duct mount via duct mount flange (requires 0.750-0.938 in [20-24 mm] drilled hole). The probe version body measures 3-33/64 in [89.13 mm].
  • Electrical Entry: 1/2" NPS thread; accessory cable gland A-151 for 5 to 10 mm diameter cable.
  • Communication Configuration: Supported baud rates include 9600, 19200, 38400, 57600, 76800, and 115200 (optional). Units can be daisy-chained to access velocity, flow data, and air temperature.
  • Approvals: BTL, CE.

Configuration Options

  • Accuracy Models: 1% or 2% accuracy (selected at order).
  • Display: Optional integral 5 digit LCD display with housing cover and overlay.
  • Remote Tooling: Portable remote display tool, Model A-435-A.
  • Certification Options: Factory calibration certificate or NIST certificate available as options.

Key Product Differences

The Series AVLV is distinguished by accuracy class and communication capability. Model numbers follow the pattern AVLV - [Accuracy] - [Mounting] - [Output] - [Options].

  • Accuracy Codes: "-1" denotes ± (1% of reading + 0.06 m/s); "-2" denotes ± (2% of reading + 0.06 m/s).
  • Mounting Code: "D" indicates Duct mount.
  • Output Codes: "A1" provides Analog universal output; "B1" adds BACnet MS/TP communication; "M1" adds Modbus® RTU/ASCII communication.
  • Display Option: The suffix "-LCD" indicates the inclusion of an integral display. Field upgradeable displays are available as accessories (Model A-AVLV-LCD).

Accessories

installation hardware

A-AVUL-MTG RPLMNT DCT MNT PLT
$8.55 / each
5 In Stock

meters/controllers

AVUL LCD UPGRADE KIT ACCY
$55.10 / each
8 In Stock
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 5ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 4ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
en-US
en_CA
Save Configuration