Taiwan 0809 090 375 | Intl +65 6415 5353 | Welcome to our new site - found a bug? Please report it here
ELC-PLC-Series
Added to Your Shopping Cart
Configuration complete.
Please add to cart to keep it or exit the configuration
Please add to cart to keep it or exit the configuration
Failed to Save Configurations, Click on Configure Button Start Again
Product Specs
<< See all Product Models| Brand |
|
| Data Interface | RS232, RS485 |
| Display Size | N/A |
| Display Type | LED |
| EMC Immunity Note | ESD Immunity: 8 kV air discharge EFT Immunity: Power Line: 2 kV Digital I/O: 1 kV Analog and Communication I/O: 250 V Damped-Oscillatory Wave: Power Line: 1 kV Digital I/O: 1 kV RS Immunity: 26 MHz to 1 GHz, 10 V/m Ground: The diameter of the grounding wire cannot be smaller than the wire diameter of terminals L and N (all ELC units should be grounded directly to the ground pole) |
| Input Current | 5 mA |
| Insulation Resistance | >5 M @ 500 Vdc, between all inputs/outputs and earth |
| Operating Humidity | 50 to 95% RH |
| Operating Temperature, Max | 55 °C |
| Operating Temperature, Min | 0 °C |
| Power Consumption | 3 to 6 W |
| Response Time | 10 ms |
| Response Time Note | About 10 ms; an adjustment range of 0 to 10,000 ms could be selected through D1020 and D1021 |
| Series ID | ELC-PLC-Series |
| Storage Humidity, Max | 5 to 95% |
| Storage Temperature, Max | 70 °C |
| Storage Temperature, Min | -25 °C |
| Supply Voltage | 24 Vdc |
| Vibration and Shock | IEC1131-2, IEC 68-2-6 (TEST Fc)/IEC1131-2 and IEC 68-2-27 (TEST Ea) |
| Weight | 0.158 kg |
| See All Specs | |
PDFs & Manuals
Accessories
accessories
ELC PROGRAMMING SOFTWARE
/ each
0 In Stock
cables
USB TO SERIAL INTERFACE
/ each
0 In Stock