OM-CP-RFVOLT2000A-Series

Wireless Voltage Data Logger with Display

  • Wireless Two-Way Communications
  • 2.5V, 15V, 30V or 160 mV Measurement Ranges
  • 160 mV Model Measures Differential Voltage
  • Digital Display Provides Instant Access to Current Readings and Statistics
OM-CP-RFVOLT2000A-Series
From  461,72
Wireless Voltage Data Logger with Display OM-CP-RFVOLT2000A-Series OM-CP-RFVOLT2000A-Series
loading all models
Product Overview
  • Alarm Note User configurable audible, on-screen, email and text (SMS) alarms, Alarm Delay: A cumulative alarm delay may be set in which the device will activate the alarm (via LED) only when the device has recorded a user specified time duration of data, Audible Alarm Functionality: 1 beep per second for reading alarm above/below threshold
  • Approvals CE, FCC, IC, KCC
  • Band Frequency 2.405 to 2.475 GHz
  • Band Frequency Note ISM band 2.405 to 2.475 GHz operation (channels 11 through 25) @ 250 kbps data rate
  • Battery life 3 yr, typical with reading interval of 15 min
  • Battery Size and Type Li-ion, 9V
  • Baud Rate 250000
  • Calibration Digital Calibration through Software
  • Calibration Date Automated
  • Configuration Omega Data Logging Software, Windows PC
  • Conversion Time 150 milliseconds
  • Data Interface Wireless, USB
  • Display LCD
  • Form factor Wall Mount
  • Height 0.95 in
  • Input Type External
  • LED Functionality Green LED blinks every 5 seconds to indicate unit is logging, Blue LED blinks every 15 seconds to indicate unit is in wireless mode, Red LED blinks every 1 second to indicate alarm condition
  • Length 3 in
  • Logging Modes Fixed interval
  • Materials Plastic
  • Measurement Type Voltage
  • Memory Modes Yes
  • Number of Measurements 1
  • Operating Temperature, Max 60 °C
  • Operating Temperature, Min -20 °C
  • Overload Protection ± 50 Volts for 2 seconds
  • Relative Humidity 0 to 95% RH non-condensing
  • RF Frequency 2.45 GHz
  • RF Frequency Note 2.45GHz IEEE 802.15.4 ultra-low power wireless transceiver with fully bi-directional communication
  • Samples,Max 32256 Samples, Interval Selectable 1 Sec to 24 hrs
  • Sensor Type Voltage Sensor
  • Series ID OM-CP-RFVOLT2000A-Series
  • Software XP SP3/Vista/7 and 8 (32 and 64-bit)
  • Start Modes Delayed Start, Immediate Start
  • Supply Power Note Ultralife 9V lithium battery included; user replaceable
  • Supply Power Type Battery
  • Time Accuracy ± 1 minute/month
  • Weight 4.1 oz
  • Width 3.5 in

Supported Applications

The Omega OM-CP-RFVOLT2000A is a wireless data logger designed to measure and record DC voltage signals. The device connects directly to DC voltage sources, making it suitable for battery usage studies, solar energy monitoring, and other DC voltage monitoring applications.

Additionally, the series can be interfaced with a wide range of voltage output sensors, including pressure sensors and CO2 sensors, as well as transmitters and other transducers. The device features an LCD screen providing instant access to current reading, minimum, maximum, and average statistics.

Operating Conditions & Performance

The OM-CP-RFVOLT2000A series measures DC voltage across four specific ranges: 2.5V, 15V, 30V, or 160mV. The device includes LED indicators for Status (Green), Wireless (Blue), and Alarm (Red) conditions.

Recalibration is recommended annually using standard points defined by the model range: 0V and 2.5V for the 2.5V model; 0V and 15V for the 15V model; 0V and 25V for the 30V model; and 0V and 100mV+/-1mV for the 160mV model.

Configuration Options

The series is available in four measurement range configurations, identified by their suffix:

  • OM-CP-RFVOLT2000A-2.5V: 2.5V measurement range.
  • OM-CP-RFVOLT2000A-15V: 15V measurement range.
  • OM-CP-RFVOLT2000A-30V: 30V measurement range.
  • OM-CP-RFVOLT2000A-160MV: 160mV measurement range.

The device features three selection buttons: Scroll, Units, and Wireless. Statistics can be reset manually via the keypad without erasing recorded data. The unit is programmable with engineering units (e.g., PSI, %, PPM) via software.

Connections & Mounting

The electrical connection utilizes a terminal block on the bottom of the device featuring one positive and one negative terminal; the 160mV model includes an additional ground terminal. The base supports tabletop mounting or wall mounting with screws.

Key Product Differences

Variants within the OM-CP-RFVOLT2000A series differ primarily by their measurement range and associated calibration points. A key distinction exists in the electrical connection: while standard models utilize a two-position terminal block (positive/negative), the 160mV model incorporates a three-position terminal block to accommodate ground connections.

Battery replacement for all variants requires part number OM-CP-BAT103.