Product Overview
  • Accuracy ± 1 %
  • Electrical Connection 1/2 in NPS female Conduit with Screw Terminal block
  • Enclosure Ratings IP10, NEMA Type 1
  • Hysteresis 10% at upper end of flow range, 30% at lower end of flow range (∆ Flow Rate to Activate/ Deactivate Switch)
  • Linear Flow Rate, Max 0 ft/s
  • Linear Flow Rate, Min 0 ft/s
  • Material Construction Option N/A
  • Materials Stainless Steel, Brass
  • Media Compatibility Liquids
  • Operating Pressure, Max 200 psi
  • Operating Pressure Note Operating Pressure: 8.6 bar (125 psi) @ 21°C (70°F), 3.4 bar (50 psi) @ 100°C (212°F)
  • Operating Temperature, Max 66 °C
  • Operating Temperature, Min 0 °C
  • Paddle Length 1.3 in
  • Pipe Size, Max 0 in
  • Pipe Size, Min 0 in
  • Pressure Drop, Max 1 psi
  • Process Connection Size 1 in
  • Process Connection Type NPT Male
  • Process Temperature, Max 121 °C
  • Process Temperature, Min 0 °C
  • Sensitivity 10% @ upper end of range; 30% @ lower end of range
  • Supply Voltage 125 / 250 Vac
  • Switch Rating 15 A
  • Switch Rating Note 15 A, ½ hp at 125 or 250 Vac 0.5 A at 125 Vdc (tungsten lamp) 0.25 A @ 250 Vdc (tungsten lamp)
  • Switch Type SPDT NO/NC, Selectable
The OMEGA® FSW-160 is the newest heavy-duty line of flow switches. The switch is used to signal, start, or stop electronically operated equipment when flow or no-flow conditions occur.
Omegas elastomeric sealing system is superior to the metal bellows that are subject to metal fatigue and corrosion. This seal system has been field-proven for over a decade. The FSW-160 can be used in pipes 1 inch and larger, with set-points as low as 4 GPM (15.2 LPM) to over 500 GPM (1893 LPM) in larger pipe sizes. The FSW160 uses a 15A SPDT micro switch that can control a 1/2 horsepower motor.