Netherlands 07077 03815 | Intl +31 (0) 7077 03815 | Welcome to our new website, found an issue or bug? Please report it here
ip211-ep211
General Purpose Current I/P or Voltage E/P to Pressure Converter
- Low Cost
- Built-in Volume Booster
- Small Size
- Field Reversible
Product Overview
- Accuracy ± 2.5 %
- Accuracy Detail Includes linearity, hysteresis and repeatability
- Electrical Connection DIN 43560 connector
- EMC Standard IEC 61000-4-3
- Enclosure Ratings IP65, NEMA Type 4X
- Enclosure Type N/A
- Flow Rate Note 12 scfm @ 100 psig 20 scfm @ 150 psig
- Input Control Signal N/A
- Materials Stainless Steel, Brass, Zinc, Epoxy, Chromated Aluminum, NBR
- Media Compatibility Clean dry air / inert gas
- Mounting Direct wall, panel, DIN rail
- Operating Temperature, Max 60 °C
- Operating Temperature, Min -30 °C
- Process Connection Size 1/4 in
- Process Connection Type NPT Female
- Series ID ip211-ep211
- Supply Pressure Sensitivity 0.1% of span per psi (±0.02% for zero-based units)
- Total Air Consumption 6 SCFH
- Volumetric Flow Rate, Max 12 SCFM
- Weight 590 g
Supported Applications
The Omega IP211 and EP211 series are general-purpose electropneumatic transducers designed to convert electrical input signals into proportional pneumatic output pressures. These devices function as current-to-pressure (I/P) or voltage-to-pressure (E/P) converters within industrial process control systems, primarily used to drive pneumatic actuators.
The IP211 models accept a 4-20 mA current signal, while the EP211 models support various DC voltage inputs including 1-5 Vdc, 0-5 Vdc, and 0-10 Vdc. The series is engineered for applications requiring high flow capacity, featuring an integral volume booster capable of up to 12 SCFM minimum flow rate at 100 psig (7 bar) supply pressure.
Operating Conditions & Performance
The IP211/EP211 series operates with a pneumatic output range spanning from low-pressure configurations such as 3 to 15 psig (0.2 to 1.0 bar) up to high-pressure ranges of 3 to 120 psig (0.2 to 8.3 bar). Specific available output ranges include:
- 3 to 15 psig (0.2 to 1.0 bar)
- 3 to 27 psig (0.2 to 1.9 bar)
- 6 to 30 psig (0.4 to 2.1 bar)
- 2 to 60 psig (0.1 to 4.1 bar)
- 3 to 120 psig (0.2 to 8.3 bar)
Performance specifications for the series include a linearity of <1.0% of span (terminal based), repeatability of <0.5% of span, and hysteresis of <1.0% of span. The supply pressure range varies by output model: general units require 3 psig (0.2 bar) above the maximum output up to 120 psig, while specific high-range models such as the 120 psig unit require a supply between 125 and 150 psig (8.6 to 10.4 bar).
For optimal stability, units should be mounted in a vibration-free location or where vibration is isolated in the x and z axes. The device dimensions are specified as 54 x 54 x 101 mm (2 1/8 x 2 1/8 x 4").
Electrical Connections & Calibration
The transducers feature a force balance design with external zero and span adjustments accessible on the front face, except for explosion-proof models. Electrical connections are made via two leads of #18 GA wire (1 ft long), color-coded black (+) and white (-). For direct-acting configurations, connect positive to the black lead; for reverse-acting, connect positive to the white lead.
Configuration Options
The series offers a broad configuration envelope covering input signal types, output pressure ranges, and hazardous location approvals. The IP211 models are designated as Current I/P converters (4-20 mA), while EP211 models serve as Voltage E/P converters with selectable voltage inputs.
Input Signal Options
- IP211 Series: 4 to 20 mA input signal.
- EP211 Series: Available in 1-5 Vdc, 0-5 Vdc, and 0-10 Vdc configurations. Specific model suffixes denote the voltage range (e.g., -5V for 0-5 Vdc, -10V for 0-10 Vdc).
Approvals & Hazardous Locations
Certain IP211 models are certified for use in hazardous locations:
- FMApproved (Intrinsically Safe): Class I, II, III, Division 1, Groups A, B, C, D, E, G. Models include suffixes such as -ISF.
- CSA Approved (Intrinsically Safe): Class I Groups A, B, C, and D; Class II Groups E, F, and G; Class III. Models include suffixes such as -ISC.
Note: Intrinsically safe ratings are not affected by recalibrating for split ranges or reverse-acting applications. FM Approved models require installation in accordance with interconnection diagrams using proper energy limiting barriers.
Process Connections & Accessories
- Pneumatic Ports: 1/4" NPT ports marked 'IN' (supply) and 'OUT' (output).
- Electrical Connection: 1/2-14 NPT conduit fitting for signal entry.
- Accessories: TX4-100 accessory provides 30.48 m (100') of 4-conductor shielded wire.
Key Product Differences
The IP211 and EP211 series are distinguished by their input signal type, output pressure range, and safety certifications. The model number structure follows the pattern: Series (IP211/EP211) - Model Variant - Output Range - Approval.
- General Purpose Models: Standard IP211 and EP211 units without hazardous location suffixes are designed for general industrial environments. These models feature accessible zero and span adjustments on the front face.
- Intrinsically Safe I/P Models (IP211 only): Suffix -ISF denotes FM Approved Intrinsically Safe, while -ISC indicates CSA Approved Intrinsically Safe. These variants are restricted to specific output ranges (e.g., 3-15 psig and 3-27 psig) as listed in the ordering chart.
- Voltage Input Variants: EP211 models differentiate input voltage via suffixes: no suffix typically indicates 1-5 Vdc, -5V indicates 0-5 Vdc, and -10V indicates 0-10 Vdc. Impedance values vary by model; for example, the IP211-X15 has a nominal impedance of 180 Ω, while EP211 models range from 500 Ω to 985 Ω depending on voltage and pressure configuration.
Positions other than vertical mounting will require recalibration of the zero adjustment. All unused ports must be plugged to maintain performance integrity.