Netherlands 07077 03815 | International +31 (0) 7077 03815 | Welcome to our new website, found an issue or bug? Please report it here
Series-V4
Added to Your Shopping Basket
Configuration complete.
Please add to basket to keep it or exit the configuration
Please add to basket to keep it or exit the configuration
Failed to Save Configurations, Click on Configure Button Start Again
Product Specs
<< See all Product Models| Brand |
|
| Applications | Fluid Measurement and Control, HVAC, Oil, Pump Control, Fluid Measurement and Control, HVAC, Oil, Pump Control |
| Electrical Connection | 3/4 in NPT male Conduit with Screw Terminal block, 3/4 in NPT male Conduit with Screw Terminal block |
| Enclosure Ratings | Hazardous Location Rated, Weatherproof, Hazardous Location Rated, Weatherproof |
| Enclosure Ratings Note | Weatherproof and Explosion-proof. **Listed with UL and CSA for Class I, Groups C and D; Class II, Groups E, F, and G. ATEX 2813 II 2 G Ex db IIB T6 Gb -20°C≤Tamb≤73°C, -20°C≤Process Temp≤73°C. EU-Type Certificate No.: KEMA 03 ATEX 2383. ATEX Standards: EN 60079-0:2012+A11:2013; EN 60079-1:2014. IECEx Certified: For Ex db IIB T6 Gb -20°C≤Tamb≤73°C. -20°C≤ProcessTemp≤73°C. IECEx Certificate of Conformity: IECEx DEK 11.0071.IECEx Standards: IEC 60079-0:2011; IEC 60079-1:2014. Zone I. Also FM approved., Weatherproof and Explosion-proof. **Listed with UL and CSA for Class I, Groups C and D; Class II, Groups E, F, and G. ATEX 2813 II 2 G Ex db IIB T6 Gb -20°C≤Tamb≤73°C, -20°C≤Process Temp≤73°C. EU-Type Certificate No.: KEMA 03 ATEX 2383. ATEX Standards: EN 60079-0:2012+A11:2013; EN 60079-1:2014. IECEx Certified: For Ex db IIB T6 Gb -20°C≤Tamb≤73°C. -20°C≤ProcessTemp≤73°C. IECEx Certificate of Conformity: IECEx DEK 11.0071.IECEx Standards: IEC 60079-0:2011; IEC 60079-1:2014. Zone I. Also FM approved. |
| Media Compatibility | Clean dry air / inert gas, Clean process / cooling water, Compatible Liquids, Inert / non-reactive gases, Oils / lubricants, Organic solvents, Water, Alcohols, Argon, Compatible Gases, Compatible Liquids, Nitrogen, Oils, Water |
| Mounting Orientation | ± 5° from Vertical, ± 5° from Vertical |
| Operating Temperature, Max | 275 °F, 275 °F |
| Operating Temperature, Min | -4 °F, -4 °F |
| Pipe Size, Min | 1.5 in, 1.5 in |
| Process Connection Size | 1 1/2 in, 1 1/2 in |
| Process Connection Type | NPT Male, NPT Male |
| Process Temperature, Max | 163 °F, 163 °F |
| Process Temperature, Min | -4 °F, -4 °F |
| Series ID | Series-V4 |
| Set Point Adjustment | Vane adjustments, Vane adjustments |
| Switch Rating | 10 A @ 125/250 Vac, 10 A @ 125/250 Vac |
| Switch Rating Note | UL, FM, ATEX and IECEx models 10 A @ 125/250 VAC (V~). CSA models: 5 A @ 125/250 VAC (V~); 5 A res., 3 A ind. @ 30 VDC(V ). MV option: 1 A @125 VAC (V~); 1 A res., .5 A ind. @ 30 VDC (V ). MT option: 5 A @ 125/250 VAC (V~). [MT and MV option not UL, CSA, FM, ATEX or IECEx], UL, FM, ATEX and IECEx models 10 A @ 125/250 VAC (V~). CSA models: 5 A @ 125/250 VAC (V~); 5 A res., 3 A ind. @ 30 VDC(V ). MV option: 1 A @125 VAC (V~); 1 A res., .5 A ind. @ 30 VDC (V ). MT option: 5 A @ 125/250 VAC (V~). [MT and MV option not UL, CSA, FM, ATEX or IECEx] |
| Weight | 1.9 kg, 1.9 kg |
| Wire Gauge | 16 AWG, 16 AWG |
| See All Specs | |