PTS4-1
Floating Point to Pneumatic Output Transducer for 20 to 25 psig Air Supply Pressure
- Converts floating point control to pneumatic output: PTS4.1 modules convert digital increase/decrease signals into proportional pneumatic pressure for pneumatic actuators.
- Selectable pressure ranges: Jumper-selectable outputs support 0-10 psig, 5-15 psig, or 0-15 psig to match common pneumatic damper and valve actuator requirements.
- Closed-loop pressure control: Onboard microprocessor and solid-state pressure transducer help maintain the last commanded branch line pressure.
- Ideal for HVAC pneumatic control: Useful for pneumatic damper motor control, pneumatic valve actuator control, compressor staging, and electric control of pneumatic actuators.
- Smooth output resolution: Full-scale pressure change occurs in 90 seconds with 255 steps of resolution for controlled pneumatic positioning.
- Flexible input compatibility: Accepts relay contact closures, transistor outputs, or triac inputs without additional accessories.
- Power-loss pressure behavior: On power failure, both valves close to shut off main air and branch line bleed, helping hold branch pressure if the line does not leak.
- Optional gauge model: PTS4.1G includes gauge capability for local branch pressure indication during setup and service.
- Panel-friendly installation: Snaptrack mounting, 90° pluggable screw terminals, removable brass fittings, and 1/4" OD poly tubing compatibility simplify installation.
- Backed by ACI quality: RoHS2 and WEEE compliant, with ACI’s two-year limited warranty.
Product Overview
- Accuracy ± 2 %
- Accuracy Detail Gauge Pressure Accuracy (Gauge Models): ± 2.5% Midscale (± 3.5% Full Scale)
- Air Consumption 2300 SCIM
- Air Supply Pressure, Max 25 psi
- Air Supply Pressure, Min 20 psi
- Applications Building and Maintenance, Pneumatic Systems
- Approvals RoHS2, WEEE
- Contact Fail-Safe No failsafe
- Control Valve 2 Valve
- Electrical Connection Screw Terminal
- Filter Furnished with integral-in-barb 80-100 micron lter (Part # PN004)
- Gauge Type No Gauge
- Height 2.95 in
- Input Note Digital Input Signal Source: Two (2) Relay Contact Closures, Transistors or TRIACs (no accessories required); Digital Input Signal Trigger Level (@ Impedance): 9-24 VAC @ 750Ω
- Input Type Floating Point
- Length 3.25 in
- Materials PVC
- Operating Humidity 10 to 95% RH, non-condensing
- Operating Temperature, Max 120 °F
- Operating Temperature, Min 35 °F
- Output Pressure Range 0 to 10 psi, 0 to 15 psi, 5 to 15 psi
- Power Consumption 3.6 VA
- Pressure Note Gauge Pressure Range (Gauge Models): 0-30 psig (0-200 kPa)
- Pulse Measurement Range 90 sec
- Sampling Rate 90 Seconds
- Series ID PTS4-1
- Spec Sheet QR URL https://www.dwyeromega.com/en-us/floating-point-to-pneumatic-output-transducer-for-20-to-25-psig-air-supply-pressure/PTS4-1/p/PTS4-1?guid=701a700000ulrduaaq&utm_source=spec-sheet&utm_medium=qr-code&utm_campaign=prd-sku-spec-sheet&utm_content=auto-generated-sku-level-spec-sheet
- Storage Temperature, Max 150 °F
- Storage Temperature, Min -10 °F
- Supply Voltage 24 Vac/Vdc
- Tightening Torque 0.5 Nm (Minimum); 0.6 Nm (Maximum)
- Tube Size 1/4 in OD x 1/8 in ID
- Weight 0.61 lb
- Width 2.18 in
- Wire Gauge 26 to 16 AWG
Supported Applications
The ACI PTS4-1 Floating Point to Pneumatic Output Transducer converts two digital signals from relay contact closures, transistors, or triac inputs into a proportional pneumatic signal. The series is designed for applications including:
- Pneumatic Damper Motor Control
- Pneumatic Valve Actuator Control
- Compressor Staging
- Electric control of any Pneumatic Actuator
The device utilizes a closed-loop electronic design where an on-board microprocessor measures signal input and a solid-state pressure transducer measures branch line pressure to automatically increase or decrease air pressure.
Operating Conditions & Performance
The PTS4-1 operates with a supply voltage of 24 VAC +/-10% at terminals | 50 or 60 Hz. It requires an air supply pressure between 20 psig (138 kPa) minimum and 25 psig (172 kPa) maximum. The pneumatic output changes full scale in 90 Seconds with a resolution of 255 steps.
Accuracy is specified as 2% @ room temperature or 3% @ full range of operating temperature. For models equipped with an optional gauge, the Gauge Pressure Range is 0-30 psig (0-200 kPa) with a Gauge Pressure Accuracy of ± 2.5% Midscale (± 3.5% Full Scale). The unit operates within an ambient temperature range of 35 to 120°F (1.7 to 48.9°C) and humidity from 10 to 95% non-condensing.
In the event of a power failure, both valves close, shutting off main air and branch line bleed. During a power brown-out, pressure output remains constant while the processor shuts down; upon restoration of proper power levels, the processor reboots and defaults the branch pressure output to 0 psig.
Configuration Options
The series supports three jumper-selectable pneumatic output ranges:
- 0-10 psig (0-68.95 kPa)
- 5-15 psig (34.47-103.43 kPa)
- 0-15 psig (0-103.43 kPa)
Pneumatic connections utilize removable brass barbed fittings for Main and Branch in a machined aluminum manifold, compatible with 1/4" O.D. nominal (1/8" I.D.) polyethylene tubing. The unit is furnished with an integral-in-barb 80-100 micron filter (Part # PN004). Electrical connections are made via 90° Pluggable Screw Terminal Blocks accepting wire sizes from 16 AWG to 26 AWG.
Available options and accessories include:
- Gauge installed at additional cost
- DIN Rail Adapter Kit (A/DRC 2.7 X 2.18)
- Transient Voltage Suppressor, Bi-directional, 56 VAC/DC, 1500W (A/D0008)
- Replacement Filter Media in Barb Fitting (A/PN004)
- 20 Gauge Metal Enclosure (ENC1)
The Snaptrack material is Polyvinyl Chloride (PVC) with a UL94 V-0 flammability rating. Agency approvals include RoHS2 and WEEE.
Key Product Differences
The series includes two primary configurations:
- PTS4.1: Floating Point to Pneumatic Output Transducer without gauge (Dimensions: L 3.25" x W 2.18" x H 1.87").
- PTS4.1G: Floating Point to Pneumatic Output Transducer with Gauge installed (Dimensions: L 3.69" x W 2.30" x H 2.95").
The PTS4.1 output is factory calibrated in all jumper selectable pressure output ranges; adjustments to zero or gain potentiometers are not permitted.
PDFs & Manuals