PX2650

Bidirectional, Differential Low Pressure Transducers

  • For Dry Gases
  • Ranges from 0.25 inH2 O to 100 inH2 O
  • For Use in Building Management, HVAC Ducts or Clean Rooms
  • Works with Unregulated Voltage Source
PX2650
From  352,68
Bidirectional, Differential Low Pressure Transducers PX2650 PX2650
loading all models
Product Overview
  • Accuracy ± 1 %
  • Accuracy Class > 0.25%
  • Accuracy Detail ± 1% BFSL at constant temperature (includes linearity, repeatability and hysteresis)
  • Compatible Meters DP41-E, DP25B-E, DP-7700
  • Compensated Temperature, Max 65 °C
  • Compensated Temperature, Min -18 °C
  • Electrical Connection Screw Terminal
  • Electrical Output 0.2 to 5.2 V
  • Enclosure Material Fire-retardant glass-filled polyester
  • Hysteresis 0.10% FS
  • Linearity Error ± 0.98%
  • Media Compatibility Air, Argon, Carbon dioxide, Helium, Hydrogen, Nitrogen, Non-corrosive Dry Gasses, Oxygen
  • Output Resistance <100 Ω
  • Output Signal Voltage
  • Measurement Pressure Type Differential
  • Process Connection Note 3 ⁄16" OD pressure fitting for 1 ⁄4" tube
  • Process Connection Size 3/16 in
  • Process Connection Type OD pressure fitting
  • Repeatability Error ± 0.05% FSO
  • Sensing Element Capacitive
  • Span Setting Adjustable Range Set to 5 Vdc ± 50 mV
  • Supply Power Note 9 to 30 Vdc unregulated
  • Supply Voltage 9 to 30 Vdc
  • Thermal Effect ± 0.06%/°C
  • Weight 85 g
  • Zero/Balance Error Set to ± 50 mV
The PX2650 series offers economical bidirectional, differential low pressure transducers ideal for measuring dry gases in building management, HVAC, and clean rooms. Featuring capacitive sensing, ±1% accuracy, and voltage output from 0.2 to 5.2 V, these transducers measure low pressure ranges from ±0.25 to ±50 inH2O with 0.10% FS hysteresis. Compatible with various non-corrosive gases including air, oxygen, and nitrogen.