DRA-TCI-RTI-Srs-Sig-Cond

DIN Rail 2 Wire Temperature Signal Conditioners/Transmitters

  • DRA-TCI-2 Thermocouple Input Model
  • DRA-RTI-2 RTD Input Model
  • Isolated
  • Linearized
DRA-TCI-RTI-Srs-Sig-Cond
From TWD 10,006
DIN Rail 2 Wire Temperature Signal Conditioners/Transmitters DRA-TCI-RTI-Srs-Sig-Cond DRA-TCI-RTI-Srs-Sig-Cond
loading all models
Product Overview
  • Accuracy ± 0.1 %
  • Accuracy Detail Including Linearity, Hysteresis and Repeatability
  • Calibration Input span: Adjusted by three DIP switches and span potentiometer, Input Zero: Adjusted by three DIP switches and Zero potentiometer; Test Terminals: 40 to 200 mV represents 4-20 mA
  • CMRR 127 dB typical DCto 60 Hz
  • DIN Rail Size 35 mm
  • Electrical Output 4 to 20 mA
  • Enclosure Ratings IP20, IP40
  • Height 3.23 in
  • Isolation 1500 Vdc or peak ac
  • Lead Compensation Error <0.1°C/20 Ohms lead resistance
  • Length 3.9 in
  • Loop Resistance Rmax (ohms) = (Vsupply - 10) / 0.02
  • Materials Polycarbonate
  • Mounting DIN rail
  • Operating Temperature, Max 70 °C
  • Operating Temperature, Min -20 °C
  • Relative Humidity 5 to 95% RH
  • Response Time 160 msec
  • Series ID DRA-TCI-RTI-Srs-Sig-Cond
  • Span Setting Adjustable Range 26 to 810°C
  • Storage Temperature, Max 85 °C
  • Storage Temperature, Min -30 °C
  • Supply Current 1 mA
  • Supply Power 10 to 40 Vdc
  • Supply Power Type DC
  • Temperature Coefficient α=0.00385
  • Temperature Stability <±0.1% of span/°C
  • Weight 130 g
  • Width 0.9 in
  • Wiring/Connector Table 2
  • Zero Setting Adjustable Range -62 to 232°C
Models DRA-TCI-2 and DRA-RTI-2 are linearized temperature transmitters that produce a 4-20 mA process signal that is directly proportional to temperature. These transmitters have exceptionally high input to output common mode rejection (CMR), a high degree of filtering that eliminates false output signals and provides a low ripple current. Model DRA-TCI-2 is available for thermocouple types J, K, T, E, R, S or B and provides exceptional temperature linearization by applying eight segment linearization circuitry. Model DRA-RTD-2 accepts 2 or 3 wire Pt-100 RTDs, alpha = 0.00385. Both models are field rangeable using a set of six internal dip switches for coarse ranging and front accessible zero and span potentiometers for fine adjustment. Test terminals are provided to monitor the transmitter’s 4-20 mA output without disturbing the actual process loop.