Taiwan 0809 090 375 | Intl +65 6415 5353 | Welcome to our new site - found a bug? Please report it here
Series-629C
Wet/Wet Differential Pressure Transmitter, Dual Sensors, 0.5% Accuracy, NEMA 4X
- Powered by either DC or AC - take advantage of most readily available power source reducing installation costs
- Optional LCD does not need a separate power supply - lowers installed cost
- Selectable voltage range - provides flexible choice for changing design or inputs for process/HVAC controllers being used to monitor and control
- Push button zero (versus trim pot) - more simple zeroing provides easy install and calibration reducing installation time and possibility of operator error
- Optional LCD indicator provides local status to identify operational condition
- Remote sensor option reduces installation labor and material
Series-629C
From
TWD
18,501
Product Overview
- Accuracy ± 0.5 %
- Accuracy Detail ± 0.5% FS (includes linearity, hysteresis and repeatability)
- Applications Filter Monitoring, Fluid Measurement and Control, Oil, Pump Control, Refrigeration, Refrigeration Equipment
- Compensated Temperature, Max 79 °C
- Compensated Temperature, Min -18 °C
- Display Type N/A
- Electrical Connection 1/2 in NPT female Conduit with Screw Terminal block
- Enclosure Ratings IP66, NEMA Type 4X
- Long Term Stability ± 1% FS/year
- Media Compatibility Fuel gases, HVAC / room air, Inert / non-reactive gases, Steam, Hydrogen, Nitrogen, Oxygen
- Mounting Note Not Position Sensitive
- Operating Temperature, Max 93 °C
- Operating Temperature, Min -18 °C
- Power Consumption max 28 mA
- Measurement Pressure Type Differential
- Process Connection Size 1/4 in
- Response Time 400 ms
- Series ID Series-629C
- Span Adjustment Push Button
- Thermal Effects 0.072%/°C
- Thermal Effects Note Avg 0.04%/°F (0.072%/°C) (includes zero and span).
- Zero Setting Adjustable Range Push buttons inside conduit enclosure
Supported Applications
The Dwyer Series 629C Wet/Wet Differential Pressure Transmitter monitors differential pressure of compatible gases and liquids. The series is designed for applications involving flow elements, coils, heat exchangers, chillers, filters, and pumps.
Operating Conditions & Performance
The Series 629C employs dual pressure sensors to convert pressure changes into an output signal with ±0.5% FS accuracy (includes linearity, hysteresis, and repeatability). The transmitter operates within a process temperature range of 0 to 200°F (-18 to 93°C) and features a response time of 400 msec. Stability is rated at ±1% FS/yr with an average thermal effect of 0.04%/°F (0.072%/°C). The enclosure meets NEMA 4X (IP66) weatherproof construction standards.
Measurement ranges span from low differential pressures to high bar values, including:
- Psi differential: 0 to 5 psid through 0 to 500 psid
- Bar differential: 0 to 0.5 bar through 0 to 30 bar
Working and over-pressure limits vary by range number; for example, the 01 range (0 to 5 psid) lists a working pressure of 10 psi and an over-pressure limit of 50 psi. Pressures exceeding the working pressure limit may cause a calibration shift of up to ±3% of full scale.
Configuration Options
The series supports multiple configuration options for housing, process connections, electrical interfaces, signal outputs, and accessories.
Housing & Mounting
- Conduit Housing: Standard NEMA 4X (IP66) conduit housing (-CH).
- Remote Sensor Options: Available with remote sensors and shielded or armored cables in lengths of 10' (-R1), 20' (-R2, -R5), or specific armored configurations (-R6). The NEMA 4X rating is maintained on the housing for non-LCD models; LCD indication options maintain NEMA 4X on sensors and housing.
Process Connections & Wetted Materials
- Connections: 1/4" male or female NPT, and 1/4" male or female BSPT.
- Materials (Without Valve): 316, 316L SS.
- Materials (With Valve Option): Buna-N, silicone grease, PTFE, brass 360, copper, and reinforced copolymer.
Electrical & Signal Outputs
- Power Supply: 2-wire: 10-35 VDC; 3-wire: 13-35 VDC or isolated 16-33 VAC (reverse polarity protected).
- Signal Output: 4-20 mA (S1) or field selectable voltage outputs of 0-5, 1-5, 0-10, or 2-10 VDC (S3).
- Load Resistance: Current output: 0 to 1250 Ω max; Voltage output: Minimum load resistance = 5 kΩ.
Options & Accessories
- Valves: Optional 3-way valve (-3V) for zeroing without removing the transmitter. Note: The -3V option is only available with the -P2 process connection, and over-pressure of all models with a 3-way valve is limited to 100 psi.
- Display: Optional field-upgradeable LCD indication (4-1/2 digit).
- Certification & Identification: Factory calibration certificate, NIST traceable certificate, and aluminum tag options are available.
Key Product Differences
The Series 629C model number structure follows the format: Series - Range - Housing - Process Connection - Electrical Connection - Signal Output - Options. Key distinctions include:
- Housing Codes: Differentiate between standard conduit housings and remote sensor configurations with varying cable lengths (10', 20') and shielding types.
- Process Connections: Selection of male/female NPT or BSPT threads determines compatibility with the optional 3-way valve, which is restricted to female NPT (-P2).
- Signal Output Codes: S1 designates a fixed 4-20 mA output, while S3 provides field-selectable voltage ranges.
PDFs & Manuals
Accessories
accessories
Stainless steel flex hose, 12" (30.48 cm) long, 1/8" male NPT connections.
TWD2,078 / each