616KX Differential Pressure Transmitters, One-Touch® Calibration

  • Simple calibration push-button sets back zero and span, saving time installing and over the service life
  • Cost effective and compact device suitable for OEM applications where space, simplicity, and value are key
  • Ranges and accuracy selection cover a wide range of applications minimizing components and determining standardizing on design
Series-616KX
From TWD 3,678
616KX Differential Pressure Transmitters, One-Touch® Calibration Series-616KX Series-616KX
loading all models
Product Overview
  • Compensated Temperature, Max 70 °C
  • Compensated Temperature, Min -20 °C
  • Display Type N/A
  • Electrical Connection Screw Terminal
  • Electrical Output 4 to 20 mA, 0 to 5 Vdc, 1 to 5 Vdc, 0 to 10 Vdc, 2 to 10 Vdc
  • Enclosure Ratings IP20, NEMA Type 1
  • Long Term Stability ± 1% FS/year
  • Loop Resistance 0 to 1250 Ω
  • Materials, Wetted Consult Factory
  • Media Compatibility Clean dry air / inert gas, HVAC / room air, Inert / non-reactive gases, Helium, Nitrogen, Non-Conductive Gases, Non-Corrosive Dry Gases, Air, Argon, Carbon dioxide
  • Mounting Note Vertical with Downward Pressure Ports
  • Number of Wires 2, 3, 4
  • Operating Temperature, Max 60 °C
  • Operating Temperature, Min -17.8 °C
  • Output Detail Field selectable
  • Output Signal Current, Voltage
  • Power Consumption max 21 mA
  • Measurement Pressure Type Differential
  • Process Connection Note Barbed, dual size to fit 1/8˝, 3/16˝ and 1/4" (3 mm and 6 mm) ID rubber or vinyl tubing
  • Process Connection Size 1/8 in, 3/16 in, 1/4 in
  • Process Connection Type Stepped Barb Fitting
  • Series ID Series-616KX
  • Span Adjustment Push Button
  • Supply Power Type AC/DC
  • Supply Voltage 10 to 35 Vdc
  • Thermal Effects Note ± 0.02% FS/°F, includes zero and span.
  • Zero Setting Adjustable Range Push button

Supported Applications

The Dwyer Series 616KX Differential Pressure Transmitter is designed for OEM applications and HVAC monitoring. The series senses the pressure of air and non-combustible, compatible gases to provide standard output signals for control systems. Documented application areas include air handlers, duct pressure measurement, variable air volume (VAV) systems, and filter monitoring.

Operating Conditions & Performance

The Series 616KX operates within an ambient temperature range of -4 °F to 159 °F (-20 °C to 70 °C). Accuracy options are available at ±0.25 % FSO, ±0.50 % FSO, ±1.0 % FSO, and ±2.0 % FSO depending on the model code (616KX-025 through 616KX-200). Stability is rated at < ±1 % / year FSO with a thermal effect of 0.02 % FS / °F (0.036 % FS / °C).

Pressure limits vary by range: 3.6 psig for ranges from 0 in w.c. to 1 in w.c. (25 Pa to 250 Pa; 2.5 mm w.c. to 25 mm w.c.) and 6 psig for ranges from 0 in w.c. to 40 in w.c. (500 Pa to 10000 Pa; 50 mm w.c. to 1000 mm w.c.). The enclosure rating is NEMA 1 (IP20), and the unit weight is 1.8 oz (51 g).

Measurement Ranges

The series supports a wide range of differential pressure spans, including:

  • 0 in w.c. to 0.1 in w.c. (25 Pa, 2.5 mm w.c.) through 0 in w.c. to 40 in w.c. (10000 Pa, 1000 mm w.c.).
  • Higher ranges up to 0 to 1000000" WC are referenced in supporting documentation.

Configuration Options

The Series 616KX offers configurable outputs, process connections, and calibration options. The transmitter features an edge-mounted push-button for zero adjustment without tools or opening the enclosure.

Output Signals & Power Requirements

  • 2-Wire Output: 4 mA to 20 mA with a power supply of 10 Vdc to 36 Vdc. Loop resistance is 0 Ohms to 1250 Ohms.
  • 3-Wire Voltage Outputs (Field Selectable): Options include 0 V to 10 V, 0 V to 5 V, 2 V to 10 V, and 1 V to 5 V. Power requirements are 17 Vdc to 36 Vdc or isolated 21.6 Vac to 33 Vac.
  • Current Consumption: 21 mA max continuous.

Process Connections & Mounting

  • Standard Ports: Barbed, male ports for flexible tubing with IDs of 1/8 in, 3/16 in, 1/4 in, 5 mm, and 6 mm.
  • Threaded Options: Optional 1/8 in female NPT or 1/8 in female BSPT threads are available via model options (-NPT, -BSPT).
  • Mounting: Designed for 35 mm DIN rail (side and back) mounting. Wall-mount holes accommodate #6 screws with a spacing of 1/4 in [6 mm] T 1/8 in [3 mm].

Options & Certifications

  • Certifications: CE, RoHS 3, Plenum Rated (UL 2043), UL94 V-0.
  • Zero Dead Band: Available as -Z1 (1 % dead band) or -Z2 (2 % dead band).
  • Documentation: Factory Calibration Certificate (-FC) and NIST Accuracy Report (-NIST) are available options.
  • Housing Accessories: Terminal Cover option (-TC).

Key Product Differences

The Series 616KX model number structure defines specific performance and configuration attributes. Accuracy is designated by codes -025 (±0.25 % FSO), -050 (±0.5 % FSO), -100 (±1.0 % FSO), and -200 (±2.0 % FSO). Directionality options include Uni-directional (-1) or Bi-directional (-2).

Range codes correspond to specific spans, such as 00 for 0 in w.c. to 0.1 in w.c., up through 12 for 0 in w.c. to 40 in w.c. Units of measure are selectable via suffixes: -IN (Inches of water column), -PA (Pascals), or -MM (Millimeters of water column). Physical dimensions differ slightly between the standard barbed variant and the NPT/BSPT threaded variants, with heights of 3 7/8 in [98.41 mm] for standard models versus 3 9/16 in [90.17 mm] for threaded versions.