Series-1630Configuration

Large Diaphragm Pressure Switch, UL/CSA, 15A, Visible Set Point, HVAC

  • Visible set point indicator simplifies operation and trouble shooting
  • Large diaphragm provides low range accuracy providing precise control
  • Current loads of up to 15 amps supports most small electrical loads supporting a broader range of HVAC and Process applications without the need for additional relays and components
Series-1630

Build your Part Number

Large Diaphragm Pressure Switch, UL/CSA, 15A, Visible Set Point, HVAC Series-1630 Series-1630
loading all models
Product Overview
  • Applications HVAC
  • Electrical Connection Screw Terminal
  • Materials, Wetted Consult Factory
  • Media Compatibility Clean dry air / inert gas, HVAC / room air, Inert / non-reactive gases, Helium, Nitrogen, Non-Corrosive Dry Gases
  • Mounting Orientation Vertical Diaphragm
  • Operating Temperature, Max 110 °F
  • Operating Temperature, Min -30 °F
  • Measurement Pressure Type Gauge
  • Process Connection Size 1/8 in
  • Process Connection Type NPT Female
  • Proof Pressure Up to 10 psi
  • Repeatability ± 1%
  • Series ID Series-1630
  • Set Point Adjustment Internal Screw
  • Switch Note 15 A @ 120-480 VAC, 60 Hz. Resistive, 1/8 HP @ 125 VAC,1/4 HP @ 250 VAC, 60 Hz
  • Switch Rating 15 A @ 120-480 Vac, 1/8 HP @ 125 Vac, 1/4 HP @ 250 Vac
  • Switch Type SPDT NO/NC, Selectable
  • Weight 1.5 kg

Supported Applications

The Dwyer Series 1630 Large Diaphragm Pressure Switch is a high-precision conventional switch designed for maximum dependability in HVAC and industrial service. The series measures differential pressure using air or non-combustible, compatible gases. It incorporates a visible set point indicator to simplify operation and troubleshooting.

Operating Conditions & Performance

The Series 1630 operates within temperature limits of -30°F (-34.4°C) for dry air or gas to 110°F (43.3°C). The switch is rated for a continuous pressure of 10 psig (68.95 kPa) and can withstand a surge pressure of 25 psig (172.4 kPa). Repeatability is specified as ±1%. Electrical capability supports up to 15 A @ 120 to 480 VAC, 60 Hz resistive loads, or 1/8 HP @ 125 VAC and 1/4 HP @ 250 VAC. The switch type is SPDT with a screw-type set point adjustment featuring an enclosed scale.

Measurement Ranges

The series offers five distinct operating ranges in inches of water column (in w.c.):

  • 1638-0: 0.05 to 0.25 in w.c.
  • 1638-1: 0.20 to 1.0 in w.c.
  • 1638-2: 1.0 to 3.0 in w.c.
  • 1638-5: 2.0 to 6.0 in w.c.
  • 1638-10: 3.0 to 12.0 in w.c.

The approximate dead band varies by model and set point, ranging from 0.04 at the minimum set point for Model 1638-0 up to 0.30 at the maximum set point for Model 1638-10.

Configuration Options

The Series 1630 is available in multiple configurations including standard pressure switches, models with conduit connections (Model 1638), and models without conduit (Model 1639). The process connection is a 1/8" female NPT. Electrical connections utilize three screw terminals for common, normally open, and normally closed circuits.

Housing and Environmental Options

Standard housings are constructed of 16 ga. steel, zinc plated, and dichromate dipped to pass a 200-hour salt spray test. The diaphragm is made of silicone rubber with a stainless steel calibration spring. Additional options include:

  • -WP: Weatherproof housing (switch must be installed at the factory).
  • -EXPL: Explosion-proof housing.
  • -MIL: Environmental construction for high humidity or government applications, utilizing a special snap switch and silicone rubber diaphragm. This configuration is designated as Model 1635 (e.g., 1635-5-MIL) and features a slightly greater dead band than the standard model.
  • -AT: Aluminum tag.
  • -ST: Stainless steel tag.

Key Product Differences

The series distinguishes between Model 1638, which includes a conduit connection (typically 7/8" diameter), and Model 1639, supplied without the conduit. The unlisted Model 1635 is specifically configured for high humidity environments or government specifications with modified internal switching components.

Installation requires mounting the switch with the diaphragm in a vertical position; re-calibration may be necessary if mounted otherwise. Agency approvals include CSA, FM, and UL listings for general service applications.

Accessories

Static Pressure Sensors for Manometers & Gages across Air Filters
From TWD224
0 In Stock
Industrial Control: Pressure Gauges, Flow Meters & Temp Controllers
From TWD194
0 In Stock

accessories

303 SS Static pressure tip with mounting flange, for 3/16" I.D. rubber or plastic tubing. 4" insertion depth, includes mounting screws
TWD498 / each
0 In Stock
4" 303 SS straight static pressure tip with flange, 1/4" hose barb.
TWD383 / each
0 In Stock
en-TW
en_TW
Save Configuration