Brand
Carbon Dioxide Accuracy ± 40 PPM + 3% rdg
Carbon Dioxide Concentration, Max 2000 ppm
Carbon Dioxide Concentration, Min 0 ppm
Carbon Dioxide Response Time 120 s (τ90)
Display Type N/A
Electrical Output 4 to 20 mA
GrossWeightValue 0.9
Measurement Type Carbon Dioxide, Temperature
Mounting Orientation Duct Mount
Operating Temperature, Max 122 °F
Operating Temperature, Min 32 °F
Output Detail 0 to (5 or 10) VDC
Output Signal Current, Voltage
Power Consumption Average: 2 W; Peak: 3.75 W
Relative Humidity 0 to 85% RH Non-Condensing
Sensor Life 15 Years
Sensor Type NDIR
Series ID Series-CDT
Supply Power Type AC/DC
Supply Voltage 19 to 28 Vac/16 to 35 Vdc
Switch Type N/A
Temperature Accuracy ± 1 °C
Temperature Input Range 32 to 122°F
Temperature Output Range 4-20 mA / 0 to (5 or 10) VDC
Voltage Output Range 0 to 5 Vdc, 0 to 10 Vdc