SCR19
SCR Power Controllers for Electrical Resistance Heaters 80 A Max
Models In Stock
SCR19
From
C$
666.49
Models In Stock
Product Overview
- Series ID SCR19
Supported Applications
The Omega SCR Power Controllers are solid-state devices designed to regulate AC power for electrical resistance heating processes. Documented applications include ovens, furnaces, and heat sealers. These controllers proportion electric power to resistive loads using silicon-controlled rectors (SCRs), trigger circuitry, fuses, and heat sinks mounted on panels.
Important operational constraints defined in the source documentation:
- Resistive Loads Only: The series is not designed for use with transformers, coils, or other inductive-type loads.
- No Patient-Connected Use: These products are not intended for patient-connected applications.
Operating Conditions & Performance
The SCR19 and related series operate within a supply voltage range of 24 to 600 Vac at frequencies of 50/60 Hz. Current ratings available across the family are 40, 60, and 80 A.
- Ambient Temperature: The specified operating ambient temperature is 30° to 122° F for listed power ratings (also cited as 0 to 50°C).
- Cooling Method: Convection cooling.
- Control Signal Input: Standard input is a 4-20 mAdc signal. All inputs are electrically isolated via optical coupling with a minimum voltage requirement of 10 Vdc and control signal isolation rated at 2500 Vac.
- Protection Features: Includes sub-cycle, current-limiting fuses; transient voltage suppression using MOV and RC circuits.
Variations in Control Method
The series offers two distinct methods of proportional control depending on the model suffix:
- Phase-Angle Firing (P): Models with a 'P' designation utilize phase-angle firing. Soft start options are available only for these models.
- Zero-Voltage Switching (Z): Models with a 'Z' designation use zero-voltage switching to minimize electrical noise and inrush current effects on the line.
Configuration Options
The series supports multiple configurations regarding phase, wiring topology, voltage levels, and control interfaces. Selection is driven by specific load requirements and installation constraints.
Phase and Wiring Configurations
- SCR19P: 1-phase, 1-line control.
- SCR19Z: 3-phase, 3-wire, delta or ungrounded wye.
- SCR39P: 3-phase, 3-line control.
- SCR39Z: 3-phase, 2-line control.
Voltage and Current Options
Line voltage is specified via a code in the model number. Available codes include:
- 02: 24 Vac
- 12: 120 Vac
- 20: 208 Vac
- 24: 240 Vac
- 48: 480 Vac
Current ratings are available in 40 A, 60 A, and 80 A increments.
Soft Start and Voltage Limit Options
For phase-angle models, soft start or voltage limit functions can be added using specific suffix codes:
- S9: Soft start 9 seconds
- S15: Soft start 15 seconds
- S30: Soft start 30 seconds
- S60: Soft start 60 seconds
- S120: Soft start 120 seconds
- V: Voltage limit
- X: No soft start or voltage limit
Manual Control Option
A manual input option module with a remote potentiometer is available. To order this configuration, the suffix '-M' must be added to the model number.
Key Product Differences
The series encompasses both SCR19 and SCR39 families, distinguished primarily by physical dimensions and phase control wiring requirements while sharing similar electrical ratings and mounting styles. Both are designed for surface mounting on panels using convection cooling.
- SCR19 Dimensions: 178 mm (7 in) height x 121 mm (4.8 in) width x 102 mm (4 in) depth.
- SCR39 Dimensions: Varies by model; SCR39Z is 178 mm (7 in) height x 244 mm (9.6 in) width, while SCR39P can be up to 365 mm (14.4 in) wide.
Differentiation between 'Phase-Angle Firing' and 'Zero-Voltage Switching' models is indicated by the model suffix ('P' or 'Z'). Diagnostic indicators are provided for shorted/open SCR conditions, reversed signal input, and mA/V status. Replacement fuses (e.g., SCR-210A015U01) correspond to specific current ratings of 40 A, 60 A, and 80 A.
Accessories
accessories
consumables
Show Ratings & Reviews
Any chance for a CAD model or dimensional drawing of a SCR39P-20-040-S9? I need to fit 4 in a panel and the overall dimensions are not enough information.
Thank you for the request. Unfortunately we do not offer CAD or other dimensional drawing. Please check manual for mounting guidelines. For cooling they require extra space air circulation.
Best regards
OMEGA
Date published: 2024-07-05
Can the high speed fuse be removed or replaced with a slower acting fuse? Having issues with the fuses blowing unnecessarily
Hi Dave
High speed fuse is for equipment safety so you would need to use same rating as provided in specifications. For help with application load questions please forward note to TEMP@OMEGA.COM.
Best regards
OMEGA
Date published: 2023-06-07
Where can I find a mechanical drawings or 3D CAD model? I need to create a model for space planning in my system.
Unfortunately Omega does not have 3D models for this to send and dimensions provided in the user's guide and on the data sheet would be the best available information.
Date published: 2024-06-21
Attempting to power a 50W heater (120V at 0.4A). When testing, the controller only seems to provide 1.2V, can you suggest any troubleshooting steps I could take. Wiring has been checked and double checked. Confused as to why at 20mA it only supplies 1.2V.
Hi SpaceConquest,
Thank you for the inquiry. Try a second light bulb in parallel or a higher wattage bulb. ( to meet the minimum load requirement). For further trouble shooting please email note to TEMP@OMEGA.COM.
Best regards,
OMEGA
Date published: 2022-09-29
What is the minimum load requirement?
Thank you for your inquiry. Minimum current load is usually 10% of the rated current for the SCR.
Date published: 2022-09-29
Can the 240V models be used at 120V? If not, is there a modification to the controller that can be made to allow it?
Hi JKHLOUKY,
Thank you for the inquiry. The SCR19Z and the SCR39Z are rated to work at levels of 1/2 the specified voltage range.
Best regards,
OMEGA
Date published: 2021-03-22
On SCR19Z-12-040 where should the brown wire labeled "LINE 2" be connected?
Thank you for your inquiry. This is connected across the load. The manual shows this connection in the manual.
Date published: 2021-09-17
What is the minimim load requirements to use the SCR19Z
Thank you for your inquiry. Minimum current load is usually 10% of the rated current for the SCR.
Date published: 2022-09-29