Product Overview
- Accuracy ± 0.2 %
- Accuracy Detail ± 0.2% FS, ± 1 digit
- CMRR 100 dB
- Cold Junction Compensation 0.05°C/°C ambient
- Contacts Twin bifurcated
- Control Characteristics Set point Limits: Limited to configured range for thermocouple and RTD; limited to scaled range; Alarms: Adjustable for high/low; selectable process or deviation; Rate (Derivative): 0 to 2400 seconds; Reset (Integral): 0 to 9600 seconds; Cycle Time: 0.2 to 120 seconds; Proportional Band: 1 to span of sensor; Dead band: Negative span to positive span of sensor; Hysteresis: 1 to span of sensor; Autotune Damping: Adjustable (low, normal, or high); Ramp to Set point: 1 to 9999 minutes; Autotune: Operator-initiated from front panel; Manual Control: Operator-initiated from front panel
- Cutout Dimensions 45 x 45 mm
- Depth Behind Panel 100 mm
- Display Size 9.2 mm (.36 in)
- Display Type 4 Digit LED
- Display Type Note Dual LED—4-digit, orange: process display; green: menu/parameter display; 9.2 mm (0.36")
- Electrical Connection Screw Terminal
- Enclosure Ratings IP65, NEMA Type 4X
- Events/Alarms 1 to 8
- Form factor 1/16 DIN
- Hardware and Software Requirements, Min CN8-SW (Optional Software): Minimum Hardware and Software Requirements: IBM PC or 100% compatible, Windows 95/98/NT; RS485 interface or RS232 to RS485 converter; Software Compatibility: CN8200 Series controllers; Software Capability: Supports up to 254 CN8200 Series controllers
- Height 53.3 mm
- Input Type Thermocouple, RTD, mA, Voltage
- Input Type Note Input Type: See input table on next page Digital Input: For remote setpoint, remote standby or ramp/soak run and hold Thermocouple Lead Resistance: 100 Ω maximum for rated accuracy Decimal Position: Selectable
- Length 8.21 mm
- Loops 0 to 99
- Measurement Type Current, Temperature, Voltage
- Measuring Range Type J (Iron-Constantan): -200 to 760°C, Type K (CHROMEGA®-ALOMEGA®): -270 to 1354°C, Type T (Copper-Constantan): -270 to 400°C, Type N (OMEGALLOY®) : -268 to 1300°C, Type R (Pt/13%Rh-Pt) : -50 to 1768°C, Type S (Pt/10%Rh-Pt) : -50 to 1768°C, Type B (Pt/30%Rh-Pt/6%Rh) : 0 to 1820°C, Type C (W/5%Re-W/26%Re) : 0 to 2315°C, Type E (CHROMEGA®-Constantan) : -150 to 1000°C, NNM 18% molybdenum vs nickel -06% cobalt : 0 to 1410°, Platinel II : -100 to 1232°C, RTD ((3-wire) 100 Ω Pt) : -200 to 850°C, RTD ((3-wire) 100 Ω Pt) : -199.9 to 375.0°C, 0 to 1V : Scalable (-1999 to 9999) selectable 1 to 5V : Scalable (-1999 to 9999) selectable 0 to 5V : Scalable (-1999 to 9999) selectable 0 to 10V : Scalable (-1999 to 9999) selectable 10 to 50 mV : Scalable (-1999 to 9999) selectable 0 to 50 mV : Scalable (-1999 to 9999) selectable 0 to 10 mV : Scalable (-1999 to 9999) selectable 0 to 100 mV : Scalable (-1999 to 9999) selectable 4 to 20 mA : Scalable (-1999 to 9999) selectable 0 to 20 mA : Scalable (-1999 to 9999) selectable
- Memory Backup Solid State
- Number of Inputs 1
- Operating Temperature, Max 55 °C
- Operating Temperature, Min 0 °C
- Ramp and Soak 8 Ramp & Soak
- Ramp Setpoint 1 to 9999 minutes
- Ramp/Soak Time 0 to 9999 minutes
- Relative Humidity 90% RH, non-condensing
- Repeatability ± 1 count
- Sampling Rate 10 Hz (10 updates/second)
- Series ID CN8200-Series
- Series Mode Rejection >70 dB
- Setpoint Resolution 1 count/0.1 count
- Supply Power Note 100 to 250V, 50/60 Hz (single-phase); 120 to 250 Vdc, 24 Vac/24 Vdc (optional)
- Temperature Stability 5 μV/°C Max
- Weight 226 g
- Width 53.3 mm
The CN8200 temperature/process controller is extremely versatile and user-friendly. The operator needs to review only those parameters relevant to the particular application during setup. A dual digital display offers optimum process information at a glance. Individual LED's identify the status of outputs, alarms, digital communications, and special options. The CN8200 features a NEMA-4X front panel and a universal power supply that accepts 100 to 250 Vac and 120 to 250 Vdc. A 24 Vac/24 Vdc power supply option is also available. Control algorithms available are P, PI, PD, PID, or ON/OFF. The autotune feature automatically sets proportional band, derivative, and integral before the process reaches setpoint. These parameters provide quick stabilization of processes with minimum overshoot, hunting, or cycling.
Eight-level ramp/soak control consisting of 8 ramps and 8 soaks is standard, and includes a decimal display on thermocouple ranges, digital display and signal filtering, and a percentage of power limit setting. The dual control outputs can be configured for a variety of control and alarm applications, and two dedicated alarm outputs are also available. The CN8200 offers a wide range of options, including RS-232 and RS-485 digital communications, five remote analog setpoint ranges, three contact/digital input modes, four transducer excitation voltages, and four auxiliary output ranges.
Eight-level ramp/soak control consisting of 8 ramps and 8 soaks is standard, and includes a decimal display on thermocouple ranges, digital display and signal filtering, and a percentage of power limit setting. The dual control outputs can be configured for a variety of control and alarm applications, and two dedicated alarm outputs are also available. The CN8200 offers a wide range of options, including RS-232 and RS-485 digital communications, five remote analog setpoint ranges, three contact/digital input modes, four transducer excitation voltages, and four auxiliary output ranges.
PDFs & Manuals
Software & Drivers
Show Ratings & Reviews
Rated 5 out of
5
by
PTElectrical from
A+
Great experience. Quick shipping. Item as described.
Date published: 2023-03-12
Rated 5 out of
5
by
Bobby100 from
Great Product
Great Product! Thanks for your quality work Omega!
Date published: 2022-01-31
Rated 4 out of
5
by
mybeer2018 from
Confusion
You should have shipped all 5 units together instead of splitting the order. No explanation provided. That just caused unnecessary confusion.
Date published: 2021-04-19