  • 4 to 20 mA, 0 to 1 Vdc, 0 to 5 Vdc or 0 to 10 Vdc Outputs
  • Accurate to ± 2.5% (20 to 80% Relative Humidity)
  • Rugged Industrial Splashproof Enclosure NEMA 13 (IP54)
  • Duct Mount Kit Included with Duct Mount and Remote Probe Models
HX92B-Srs-RH-Sig-Cond
Depuis C$ $589.84
Modèles en stock
Relative Humidity Signal Conditioner/Transmitter with Probe HX92B-Srs-RH-Sig-Cond HX92B-Srs-RH-Sig-Cond
loading all models
L'aperçu du produit
  • Accuracy ± 4 %
  • Cable Diameter 6.73 mm
  • Enclosure Ratings IP54
  • Materials, Wetted Polycarbonate
  • Measurement Type Humidity
  • Relative Humidity 0 to 100% RH
  • Relative Humidity Response Time 8 sec
  • Repeatability ± 0.1% RH
  • Sampling Rate 0.25 Hz (4 seconds between updates)
  • Supply Power Type DC
  • Temperature Measurement, Max 75 °C
  • Temperature Measurement, Min -30 °C
  • Wire Gauge 22 to 14 AWG
The HX92B Series transmitters provide remote and on-site monitoring of relative humidity. It is available with either voltage or 2-wire current output. The transmitter output is linearized and temperature compensated. Current output models enable placing of the transmitter at a remote location virtually any distance away from the measuring device. All models use an accurate digital sensor. A stainless steel mesh type filter, easily removable for cleaning, protects the sensor. Mounting screws are easily accessible inside the rugged, polycarbonate enclosure which protects the electronics to NEMA 13 (IP54) specifications.

Specifications
Input Power
4 to 20mA: 9 to 30Vdc @ 50mA
0 to 1V: 9 to 30Vdc @ 50mA
0 to 5V: 9 to 30Vdc @ 50mA
0 to 10V: 12 to 30Vdc @ 50mA
Measuring Range: 0 to 100% RH
Accuracy: ± 2.5% from 20 to 80% RH; ± 3.5% from 5 to 20% and 80 to 95% RH; ± 4% from 0 to 5% and 95 to 100% RH
Output:
HX92BC: 4 to 20 mA for 0 to 100% RH
HX92BV0: 0 to 1 Vdc for 0 to 100% RH
HX92BV1: 0 to 5 Vdc for 0 to 100% RH
HX92BV2: 0 to 10 Vdc for 0 to 100% RH
Relative Humidity Temperature Compensation: -30 to 75°C (-22 to 167°F)
Relative Humidity Response Time: 8 second typical
Repeatability: ± 0.1% RH
Sample Rate: 1 sample every 4 seconds
Housing: Gray polycarbonate, NEMA 13 (IP54)
Connections: Liquid-tight nylon with neoprene gland, for 2.29 to 6.73 (0.09 to 0.265")diameter cable; internal 5 position terminal block accepts 14 to 22 gauge wire
Dimensions:
HX92B(*) (without Probe): 65 L x 50 W x 34.8 D mm (2.56 x 1.97 x 1.37")
TP-SP (Short Probe): 16 dia. x 71.88 L mm (0.63 x 2.83")
Weight:
HX92B(*): 124 g (4.4 oz)
HX92B(*)-D: 132 g (4.7 oz)
HX92B(*)-RP1: 230 g (8.1 oz)