日本 +81 3 6822 0370 | 新しいウェブサイトへようこそ。問題やバグを見つけましたか?こちらからご報告ください
Series-RHPX
湿度・温度トランスミッター – 2%/3% 精度、オプションLCD、HVACなど
습도 및 온도 송신기 – 2%/3% 정확도, 옵션 LCD, HVAC 등- 複数のオンボードセンサーにより設置コストを削減
- UV評価済み屋外エンクロージャによりメンテナンスを最小限に
- UL 2043準拠でプレナムスペースへの設置が可能
- 取り外し可能な端子台、取り付けられた蓋、ケーブル管理により簡単設置
製品の概要
- 電気接続 取り外し可能なネジ式端子台
- エンクロージャーの定格 IP66
- 材料 UL 94 V-0
- 動作温度(最高) 140 °F
- 動作温度(最低) -4 °F
- プロセス接続サイズ 1/2インチ NPS ねじ、ケーブルグランド付属
- 相対湿度 0~100% RH
- シリーズID Series-RHPX
- 最大保管温度 158 °F
- 保管温度(最低) -22 °F
- 熱抵抗値 -40〜60°C
Supported Applications
The Dwyer Series RHPX Humidity and Temperature Transmitter monitors humidity and temperature for building control functions. The series is designed to support applications in building energy management systems, commercial HVAC systems, clean rooms, museums, and data centers.
In addition to relative humidity and temperature measurements, the transmitter can be configured to supply absolute or relative humidity, dew point, and enthalpy calculations.
Operating Conditions & Performance
The Series RHPX utilizes capacitive polymer sensors for humidity measurement across a range of 0 % to 100 % humidity. Temperature is measured from -40 °C to 60 °C (-40 °F to 140 °F). Humidity sensor accuracy is model specific, rated at ±2 % or ±3 %, at 10 % - 90 % RH and 25 °C (77 °F).
Temperature sensor performance varies by element type:
- Solid State Band Gap: ±0.9°F @ 77°F (±0.5°C @ 25°C)
- Thermistor: ±0.2°C @ 25°C (±0.36°F @ 77°F) for analog models only
- RTD: DIN Class B; ±0.3°C @ 0°C (±0.54°F @ 32°F) for analog models only
The operating temperature range is -40°C to 60°C (-40°F to 140°F); with LCD: -20°C to 60°C (-4°F to 140°F). Storage temperatures are rated from -40°C to 70°C (-40°F to 158°F), or -30°C to 70°C (-22°F to 158°F) with LCD. The enclosure material is UL 94 V-0 and carries an IP66 rating.
Configuration Options
The series offers extensive configuration options for enclosures, sensor configurations, outputs, and passive temperature inputs.
Enclosure & Sensor Configurations
Housing styles include small (S) or large (L) enclosures. RH sensor configurations support:
- Bronze sintered filter (B)
- Duct mount with plenum plastic probe and hydrophobic filter (D) or rapid response filter (E)
- Duct mount with SSTL probe and radiation filter (F) or rapid response filter (G)
- HDPE filter with cover (S), without cover (W), or factory installed solar radiation shield (H)
- Remote humidity sensor (-R models only, available with 1.2 m to 4.9 m cable lengths)
Outputs & Communication
Analog output models provide field-selectable signals of 4-20 mA or 0-5 V dc, 0-10 V dc at 5 mA max for both humidity and active temperature. Communicating models support BACnet MS/TP protocol or Modbus® RTU with supported BAUD rates from 9600 to 115200.
Passive Temperature Sensors
Analog models can accept passive temperature inputs including:
- Solid state band gap (Types II and III)
- Thermistor: Curves A, B, and F
- Platinum RTD DIN 385 or Balco 1K: Curves D and E
Additional Options & Accessories
An optional two-line alphanumeric display (LCD) is available. The series supports NIST traceable calibration certificates, a six-plate solar radiation shield (RHRS), duct mount adapter plates (A-RHPX-PLATE), and depth adjustment brackets (A-RHPX-DEPTH).
Key Product Differences
The Series RHPX is distinguished by accuracy class (-2 for 2 % RH, -3 for 3 % RH) and enclosure size. Analog models support passive temperature sensor inputs which are not available on communicating models. Remote sensor configurations (-R) require specific cable length options (04, 08, 12, or 16). UL 2043 compliance is limited to specific wall mount and duct mount model combinations as defined in the ordering guide.
アクセサリー
accessories
Bouclier solaire à 6 plaques pour transmetteurs RH version filtre fritté.
C$85.27 / each
0 在庫あり