1-800-663-4209 | Welcome to our new website, found an issue or bug? Please report it here
TX60
Smart and Programmable Linearized Transmitters
Transmetteurs linéarisés intelligents et programmablesThe TX60 series has been discontinued. Please see the TX86 as a possible alternative or contact our Data Acquisition Engineering department
- 2 Wire 4-20 mA Output
- TX62 TX64 Models for Thermocouple and RTDs
- TX63 TX65 Models for mV, mA, V, Resistance
- Input to Output Isolation
Product Overview
- Accuracy ± 0.05 %
- Accuracy Detail Transmitter Accuracy:±0.05% of the millivolt or Ω equivalent reading, or the accuracy from the table below, whichever is greater; plus ±0.05% of the span, if using a thermocouple sensor, allow a cold junction measurement error of ±0.5°C (±0.9°F), accuracy includes repeatability, hysteresis, load and ambient temperature Thermocouple Type: J: ±0.2°C K: ±0.2°C T: ±0.2°C E: ±0.2°C R: ±0.6°C S: ±0.6°C B: ±0.8°C N: ±0.2°C RTD Accuracy: ±0.1°C Voltage Accuracy: ±0.008 mV
- Additional Features 1 Programmable temperature transmitter
- Calibration Adjustment 100 % sensor range
- CMRR 120 dB
- Cold Junction Compensation ±0.5°C
- Diagnostics Every 3 seconds, self-checks for zero, span, cold junction, calibration references, malfunction and sensor failure
- Electrical Output 2-wire, 4 to 20 mA
- EMC Immunity Note RFI Effect: <0.5% rdg (SAMA PMC 33.1c test) 20 kHz to 1000 MHz, 10 V/meter
- Input Control Signal -15 to 160 mV
- Isolation 850 Vdc or peak ac
- Linearity Error ±0.05°C
- Load Resistance 250 Ω
- Long Term Stability < 0.05% of reading plus ±5 µA per year
- Operating Temperature, Max 75 °C
- Operating Temperature, Min -40 °C
- Output Signal Current
- Repeatability One-half of accuracy
- Resolution ±2.5 µA
- Response Time 0.25 sec; Update Time: 0.15 sec, digital, 1 sec
- Response Time Note Analog 0.25 second typical; digital 1 second, typical to 95% of final value, 5 seconds to stated accuracy (Response to Step Input)
- Reverse Voltage 42 Vdc applied with either polarity
- RTD Type 100 Ω Pt Sensor,120 Ω Ni Sensor
- Sensor Break Detection Analog, user settable to 21 mA, 3.9 mA or “OFF”, digital
- Series ID TX60
- Start Up Time <5 sec
- Storage Temperature, Max 85 °C
- Storage Temperature, Min -50 °C
- Supply Power Note Minimum supply voltage under load, Vs = 12 + R (load in kΩ) X 23 mA; for digital operation
- Supply Power Type DC
- Supply Voltage 12 to 42 Vdc
- Temperature Compensation Automatic compensation to 20°C/hour change, Self-correcting over operating temperature range
- Temperature Measurement Range J: -210 to 1200°C, K: -270 to 1372°C, T: -270 to 400°C, E: -270 to 1000°C, R: -50 to 1768°C, S: -50 to 1768°C, B: 43 to 1820°C, N: 0 to 1300°C, RTD: -200 to 850°C
- Thermocouple Type J, K, T, E, N, R, B, S
- Weight 340 g
La série TX60 n'est plus commercialisée. Veuillez consulter la série TX86 comme alternative possible ou contacter notre service d'ingénierie d'acquisition de données.
Les transmetteurs programmables TX62 et TX64 fournissent un signal isolé de 4 à 20 mA linéarisé en fonction de la température ou de l'entrée de processus.
Les transmetteurs programmables TX62 et TX64 fournissent un signal isolé de 4 à 20 mA linéarisé en fonction de la température ou de l'entrée de processus.