Passer à la recherche Passer au contenu principal Passer à la navigation

Besoin d'aide? Appelez-nous: 1-800-663-4209

Nous avons remarqué que vous êtes dans , veuillez visiter votre site local en cliquant sur le lien ci-dessous pour des offres et un support régionaux.

Model-BTK2

Kit de test de reflux hydronique – Assemblage 3 vannes et manomètres, vannes en laiton, mallette

  • Compatible with ASSE, AWWA, CSA, FCCC, HR-USV, and NEWWA recommended test procedures for hydronic systems
  • Features a 4.5˝ diaphragm differential pressure gauge (0–15 psid) and a 1.5˝ in-line pressure gauge (0–200 psig)
  • Comes with three color-coded hoses, brass adapter fittings, elastic mounting cord, and a rugged polyethylene carrying case
  • PTFE-lined brass ball valves and a large, easy-grip needle valve ensure quick, smooth adjustments in any testing environment
Model-BTK2
À partir de C$ 2 501.80
Kit de test de reflux hydronique – Assemblage 3 vannes et manomètres, vannes en laiton, mallette Model-BTK2 Model-BTK2
loading all models
Aperçu du produit
  • Précision 4,5˝ manomètre : ±2 % PE ; 1,5˝ manomètre : ±3-2-3 % PE
  • Note sur la pression d'éclatement Manomètre 4,5" : 15 psi ; manomètre 1,5" : 200 psi
  • Hauteur 9 in
  • Kit Test de prévention des refoulements
  • Description du kit Comprend : assemblage de 3 vannes, manomètre de pression différentielle de 4,5˝ (attaché), manomètre de pression en ligne de 1,5˝ (attaché), trois tuyaux de 3´, trois ensembles de raccords adaptateurs en laiton, corde élastique, ruban de plombier, mallette de transport en polyéthylène
  • Longueur 9 in
  • Matériaux en contact avec le fluide Aluminium anodisé, Laiton, Buna-N (NBR), PTFE, Caoutchouc
  • Température de fonctionnement, max 210 °F
  • Remarque concernant la pression 4,5˝ manomètre : Différentiel ; 1,5˝ manomètre : Manomètre
  • ID de série Model-BTK2
  • Poids 8.9 lb
  • Largeur 16 in

Supported Applications

The Dwyer Model BTK2 Backflow Prevention Test Kit is designed for testing hydronic systems using procedures recommended by ASSE, AWWA, CSA, FCCC, HR-USV, and NEWWA. The kit supports field testing of pressure vacuum breakers, reduced pressure principle backflow preventers, and double check valve assemblies.

Operating Conditions & Performance

The Model BTK2 operates within a process temperature limit of 210°F (99°C) with a maximum pressure rating of 175 psi (12 bar). The series includes two distinct measurement ranges: a 4.5" diaphragm differential pressure gage covering 0 to 15 psid (0 to 1 bar), and a 1.5" in-line pressure gage covering 0 to 200 psi (0 to 14 bar). Accuracy specifications are ±2% FS for the 4.5" gage and ±3-2.3% FS for the 1.5" gage.

Configuration Options

The Model BTK2 is supplied as a complete assembly in a durable polyethylene carrying case measuring 9" H x 16" W x 9" D (228 mm H x 406 mm W x 228 mm D) with a weight of 8.9 lb (4 kg). The kit includes three valves and the following components:

  • Three color-coded hoses, each 3' long
  • Three sets of brass adapter fittings for standard size test cocks
  • An elastic cord for hanging or mounting the unit in various areas
  • A large needle valve and PTFE-lined brass ball valves to simplify adjustment procedures

The wetted materials across the assembly include anodized aluminum (4.5" gage), Buna-N diaphragm, brass for the 1.5" gage, ball valves, needle valve, hose couplings, and adaptors, with rubber hoses.

Key Product Differences

The Model BTK2 is a single-configuration series identified by part number BTK2. The kit requires no routine maintenance but should be routinely checked for calibration; it is not field serviceable and must be returned to the manufacturer if repair is needed.

  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 4ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 4ms
  • QUESTIONS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;
fr-CA
fr
Enregistrer la configuration