Besoin d'aide? Appelez-nous: 1-800-663-4209
Balco-Duct-No-Box
Balco Duct Sans Boîtier
- Unités de toit
- Surveillance des températures d'alimentation/d'évacuation/de retour/d'air mélangé
Balco-Duct-No-Box
À partir de
Aperçu du produit
- Précision 70 °F (21,1 °C) : +/- 1 %
- Option d'étalonnage N/A
- Connexion électrique Câbles pigtail
- Raccord Polyamide 66 (nylon haute performance)
- Longueur d'insertion 12 in
- Isolation Téflon gravé (PTFE) Fils colorés
- Humidité de fonctionnement 10 à 95 % HR ; sans condensation
- Température de fonctionnement, max 115 °C
- Température de fonctionnement, min -40 °C
- Diamètre de la sonde 0.25 in
- ID de série Balco-Duct-No-Box
- Matériau de la gaine Acier inoxydable 304
- Plage de mesure de la température -40 à 115 °C
- Type de capteur de température RTD Balco 1 kΩ
- Calibre du fil 22 AWG
Supported Applications
The ACI Balco Duct No Box series is a single-point temperature sensor designed for use with electronic controllers in commercial heating and cooling building management systems. The duct style sensor is intended for smaller duct applications, where the probe tip should be positioned in the approximate center of the duct to ensure accurate readings.
Installation guidelines specify that the duct probe should be placed three to four duct segments down from any bend or obstructions and away from 90° bends. The sensor must be mounted on the top or sides of the duct work; mounting on the bottom risks damage due to moisture accumulation. For larger ducts, ACI references rigid or bendable copper averaging sensors for increased sensing points.
Operating Conditions & Performance
The series operates within a process temperature range of -40 to 115°C (-40 to 239°F). The storage temperature range is documented as -40 to 85°C (-40 to 185°F), and the operating humidity range is 10 to 95% RH, non-condensing.
Performance specifications for the Balco RTD sensor include:
- Sensor Output: 1000 Ohms nominal at 70°F (21.1°C).
- Accuracy: +/- 1% at 70°F (21.1°C).
- Response Time: 8 Seconds nominal for a 63% step change.
- Sensor Stability: +/- 0.05% after 1000 Hours @ 150°C (302°F).
The sensor utilizes ACI's double encapsulation process with high-quality, thermally conductive epoxy to eliminate moisture effects and increase thermal response times.
Configuration Options
This series is configured as a "Duct without Box" (DO) model featuring a mounting flange only. The probe diameter is 0.250" (6.35mm), constructed from 304 Stainless Steel, with a galvanized steel flange.
Probe Lengths
The series supports the following insertion lengths to accommodate various duct widths:
- 4" Probe
- 6" Probe
- 8" Insertion Length
- 12" Insertion Length
- 18" Insertion Length
Lead Wire and Cable Options
Sensors feature etched Teflon (PTFE) colored leads with silver-plated copper conductors. Standard lead lengths are 14" for 4", 6", and 8" probes, and 24" for 12" and 18" probes. Conductor size is 22 AWG (0.65mm).
Optional plenum-rated cable configurations include:
- 6'CL2P: 6 ft (1.83m), 2 Conductor Plenum Rated Cable
- 10'CL2P: 10 ft (3.05m), 2 Conductor Plenum Rated Cable
- 20'CL2P: 20 ft (6.10m), 2 Conductor Plenum Rated Cable
Materials and Approvals
The fitting material is Polyamide 66 (High Performance Nylon) with a UL94-HB flammability rating. The included foam pad is made of Neoprene/EPDM/SBR Polymer, rated UL94-HBF; FMVSS-302; MIL-R-6130C. Agency approvals include CE, RoHS2, and WEEE.
Key Product Differences
The primary variation within this series is the probe insertion length (4", 6", 8", 12", or 18") selected to match duct dimensions. Additionally, models are available with standard etched PTFE leads or extended plenum-rated cable options (-CL2P suffixes). An optional NIST Certificate (3 Points) is available for custom ordering.
Model numbers follow the format A/ - - - - - . For example, a 4" probe with standard leads is ordered as A/BALCO-DO-4", while a version with a 6-foot plenum cable is A/BALCO-DO-4"-6'CL2P.
PDF & Manuels
Afficher les évaluations et les avis