Besoin d'aide? Appelez-nous: 1-800-663-4209
RT-3000-Series
ACI RT-3000 Duct Smoke Detector Series for HVAC Smoke Detection and System Protection
- NEMA 4X weatherproof, corrosion-resistant enclosure
- Supports remote alarms, indicators, and test/reset stations
- Horizontal or vertical mounting flexibility
- Designed to meet HVAC and NFPA smoke detection requirements
RT-3000-Series
À partir de
Aperçu du produit
- Vitesse de l'air, max 4000 FPM
- Vitesse de l'air, min 100 FPM
- Remarque sur la conformité UL Listed (UL268A, UROX) File # S2829; CSFM Listed (3240-1004:121)
- Connexion électrique Borne à vis
- Remarque concernant le matériau du boîtier Grey plastic backbox, white plastic cover (Makrolon 94V-0)
- Caractéristiques nominales du boîtier NEMA Type 4X
- Hauteur 2.25 in
- Longueur 13.5 in
- Courant, max Remarque Standby: 24 Vdc: 45 mA, 24 Vac: 122.6 mA, 115 Vac: 31 mA, 230 Vac: 17 mA; Alarm: 24 Vdc: 100 mA, 24 Vac: 251 mA, 115 Vdc: 50 mA, 230 Vac: 29 mA
- Remarque concernant le montage 7" exhaust tube, FAST Tube sectional sampling tube starter, sampling tube end cap, mounting template, test magnet, and mounting hardware included
- Humidité de fonctionnement 10 to 93% RH (@32ºC), Non-Condensing / Non-Freezing
- Température de fonctionnement, max 60 °C
- Température de fonctionnement, min -20 °C
- Relais Remarque Alarm Relay Contacts: 2 sets form "C" rated at 10 Amps @ 125 Vac; 1 set form "A" rated at 1 Amp @ 30 Vdc, Trouble Relay Contacts: 1 set form "C" rated at 10 Amps @ 125 Vac; 1 set form "B" rated at 7 Amps
- Type du capteur Photoélectrique
- ID de série RT-3000-Series
- Poids 3.5 lb
- Largeur 5.5 in
- Calibre du fil 24 à 14 AWG
The ACI RT-3000 Duct Smoke Detector helps prevent smoke recirculation through HVAC systems. Featuring a NEMA 4X weatherproof enclosure, flexible mounting options, air sampling tubes, and compatibility with remote alarm and test accessories, it delivers reliable smoke detection indoors and outdoors.