Current to pressure transducer, 4-20 mA input, 3-15 psi (20-100 kPa) output.

Added to Your Shopping Cart
Configuration complete.
Please add to cart to keep it or exit the configuration
Please add to cart to keep it or exit the configuration
Failed to Save Configurations, Click on Configure Button Start Again
Product Specs
<< See all Product ModelsBrand |
![]() |
Air Supply Pressure, Max | 100 psi |
Air Supply Pressure, Min | 3 psi |
Electrical Connection | 1/2 in NPT female Conduit with Screw Terminal block |
Exhaust Capacity Note | 2 SCFM (3.4 m3 /h) at 5 psig (35 kPa) above 20 psig (140 kPa) set point |
Flow Rate Note | 4.5 scfm (7.6 m3/h ANR) at 25 psig (175 kPa) supply; 12 scfm (20 m3/h) at 100 psig (700 kPa) supply |
Hazardous Classification | CE, FM |
Hysteresis | < 1% of span |
Impedance | 180 Ω |
Input Type | mA |
Linearity | < ±0.75% of span |
Measurement Pressure Type | Gauge |
Media Compatibility | Clean Dry Air |
Operating Temperature, Max | 140 °F |
Operating Temperature, Min | -20 °F |
Output Pressure, Max | 15 psi |
Output Pressure, Min | 3 psi |
Process Connection Size | 1/4 in |
Process Connection Type | NPT Female |
Repeatability | < 0.5% of span |
Supply Power Note | Loop powered |
Supply Pressure Sensitivity | < ±0.1% of span per psig (< ±0.15% of span per 10 kPa) |
Total Air Consumption | 0.03 SCFM |
Volumetric Flow Rate, Max | 4.5 SCFM |
Weight | 2.1 lb |