1-800-663-4209 | Your feedback matters, take a quick survey Website Feedback
TXUN-FD
Field Mounted Hart Protocol Enabled Temperature Transmitter

Choose a Variant
Input Type
Volume discounts available
Volume Discount Schedule
Quantity | Price each |
---|---|
1-4 | $1,499.19 |
5-9 | $1,424.23 |
10-24 | $1,394.25 |
25-49 | $1,334.28 |
50-99 | $1,304.30 |
100+ | $1,274.31 |
Added to Your Shopping Cart
Configuration complete.
Please add to cart to keep it or exit the configuration
Please add to cart to keep it or exit the configuration
Failed to Save Configurations, Click on Configure Button Start Again
Product Specs
<< See all Product ModelsBrand |
![]() |
Accuracy | ± 0.05 % |
Additional Features 1 | Explosion Proof Aluminum/Stainless Steel Housing |
Approvals | EU RO Mutual Recognition Type; Approval: MRA0000009; ATEX 2014/34/EU: DEKRA 15 ATEX 0058 X; IECEx: IECEx DEK 15.0039 X; FM: FM16US0009X/FM16CA0010X; CSA: 70024231 EAC Ex TR-CU 012/2011: RU C-DK.GB08.V.01316; INMETRO: DEKRA 15.0014 X; NEPSI: GYJ15.1336X, GYJ15.1337X and GYJ15.1338X; SIL: Hardware assessed for use in SIL applications Authority Requirements: EMC: 2014/30/EU, EAC: TR-CU 020/2011 |
Calibration Adjustment | ± 50 % Max |
Calibration Temperature, Max | 28 °C |
Calibration Temperature, Min | 20 °C |
Data Interface | HART 7, HART 5 |
Dimensions Note | Aluminum: 109.3 H x 145 W x 126 D mm, Stainless: 107.4 H x 145 W x 124 D mm Dimensions: Ø 110 mm |
Display | LCD |
Display Note | 96 x 64 pixels Resolution, Selectable ON/OFF and Selectable white or red colour Backlight Number of Digits: 5 |
EMC Immunity Note | Standard EMC Imunity: <±0.1% of span; Extended EMC Immunity: NAMUR, NE21, A Criterion, Burst: <±1% of span; Wire Size: 0.13 x 1.5 mm² |
EMC Standard | EN61010-1, EN61326-1 |
Electrical Output | 4 to 20 mA |
Enclosure Ratings | IP54, IP66, IP68, NEMA Type 4X |
Height | 109 mm |
Input Control Signal | -800 to 800 mV |
Input Control Signal Note | Min. Measurement Range (Span): 2.5 mV |
Input Resistance | 10 MΩ |
Input Type | Thermocouple, RTD, Resistance, Voltage |
Isolation | Test/Working: 1.5 kVac/50Vac |
Length | 104 mm |
Load Resistance | ≤ (Vsupply - 12) / 0.023 Ω |
Long Term Stability | ±0.1% of span/year |
Operating Temperature Note | -40 to 85°C (with Silicone O-ring),-20 to 85°C (with FKM Oring) |
Operating Temperature, Max | 85 °C |
Operating Temperature, Min | -40 °C |
Output Detail | Signal Range: 4 to 20 mA,Min. Signal Range: 6 mA,NAMUR NE43 Upscale/Downscale: 23 mA/3.5 mA |
Output Load | ≤ (Vsupply - 10) / 0.023 Ω |
Output Signal | Current |
Potentiometer Input Range | 0 to 7000 Ω |
Programmable Functions | HART Setup |
RTD Input Note | Cable Resistance, Per Wire: 50 Ω; Sensor Current: 0.2 mA |
RTD Type | 50/100/200/250/500/1000 Ω Pt Sensor, 50/100/120/1000 Ω Ni Sensor |
Relative Humidity | 0 to 100% RH Condensing |
Resolution | Input Signal Dynamics: 22 bit; Output Signal Dynamics: 16 bit |
Response Time | 1 to 60 sec; Update Time : 440 msec |
Screw Terminal Torque | 0.4 Nm |
Sensor Break Detection | Programmable 3.5 to 23 mA |
Signal/Noise Ratio | > 60 dB |
Start Up Time | 5 Sec |
Storage Temperature, Max | 85 °C |
Storage Temperature, Min | -40 °C |
Supply Power Note | Intrinsically Safe: 10 (12 - with backlight)...30 Vdc, Other: 10 (12 - with backlight)...35 Vdc |
Supply Power Type | DC |
Supply Voltage | 10 to 30 Vdc |
Temperature Measurement Range | J: -100 to 1200°C, K: -180 to 1370 °C, T: -200 to 400 °C, E: -100 to 1000 °C, R: -50 to 1760 °C, S: -50 to 1760 °C, N: -180 to 1300 °C, B: 0 to 1820 °C, W3: 0 to 2300 °C, W5: 0 to 2300 °C, L: -200 to 900 °C, LR: -200 to 800 °C, RTD: -200 to 850 °C |
Thermocouple Type | J, K, T, E, R, S, B, C, N, L, U, D, LR |
Vibration | ±4g |
Vibration Note | EC 60068-2-6; 2 to 25 Hz: ±1.6 mm; 25 to 100 Hz: ±4 g |
Weight | 1.3 kg |
Weight Note | Aluminum: 1.3, Stainless: 2.8 |
Width | 23.5 mm |
Wire Type | Stranded |
See All Specs |