1-800-663-4209 | Welcome to our new website, found an issue or bug? Please report it here
HX200-Srs-TRH-Sig-Cond
Duct,Wall,Remote Mount Temp,Humidity,& Dewpoint Transmitters
Models In Stock
- High Accuracy with Certificate of Calibration
- High Temperature Sensor to 200°C (392°F) (at 0% RH)
- High Pressure Sensor to 750 psi (51.7 bar)
- Switchable for Dew Point or Humidity
HX200-Srs-TRH-Sig-Cond
From
$
1,143.24
Models In Stock

Product Overview
- Accuracy ± 1 °C (± 1.8 °F)
- Accuracy Detail ± 1.0°C from -20 to 40°C (-4 to 104°F); ± 3.0°C below -20°C (-4°F)
- Additional Features 1 NIST traceable calibration certificate included, Selectable C or F
- Dew Point Temperature, Max 40 °C
- Dew Point Temperature, Min -60 °C
- Display Type 2 line LCD
- Electrical Output 4 to 20 mA
- Filter Stainless Steel
- Length 88.9 mm
- Mounting Holes Center Length 78.7 mm
- Operating Temperature, Max 200 °C
- Output Detail Single Output: 4 to 20 mA loop powered (relative humidity or dew point)
- Pressure Limits Up to 750 psi
- Pressure, Min 0 psi
- Pressure Note Maximum Sensor Pressure Rating
- Probe Diameter 1.27 cm
- Probe Length 10.16 cm
- Process Connection Size 1/2 in
- Process Connection Type NPT Male and Female
- Relative Humidity 1 to 95%
- Resolution 0.1
- Sensor Material 304 Stainless Steel
- Supply Power Note 4 to 20 mA loop powered, 2-wire 24 Vdc (typical) 12 to 28 Vdc
- Supply Power Type Loop Powered
- Supply Voltage 12 to 28 Vdc
- Weight 1.8 kg
- Width 63.5 mm
The HX200 is a high accuracy calibrated dew point or humidity transmitter. The remote sensor is designed to work at temperatures as high as 200°C (392°F). This high accuracy sensor is also built to withstand up to 750 psi. These transmitters are perfect for applications such as compressed air, dryers and environmental chambers.
Specifications
Dew Point: -60 to 40°C (-76 to 104°F)
Relative Humidity: 0 to 95% RH (non-condensing) unit displays dew point or humidity, as well as temperature
Maximum Sensor Pressure Rating: 750 psi (51.7 bar)
Sensor Body Material: 304 SS
Maximum Operating Temperature: 200°C (392°F) (at 0% RH)
Mesh Filter Top: Stainless Steel
Single Output: 4 to 20 mA loop powered (relative humidity or dew point)
Dew Point Accuracy: ± 1.0°C from -20 to 40°C (-4 to 104°F); ± 3.0°C below -20°C (-4°F)
Relative Humidity Accuracy: ± 1% RH from 15 to 40°C (59 to 104°F), 0 to 90% RH (non-condensing); ± 2% RH below 15°C (59°F) or above 40°C (104°F)
Display: 2 line LCD
Resolution: 0.1
Power: 4 to 20 mA loop powered, 2-wire 24 Vdc (typical) 12 to 28 Vdc
Dimensions (Enclosure): 88.9 L x 63.5 W mm (3.5 x 2.5") Mounting Center: 78.7 mm (3.1")
Dimensions of Probe:
Length: 10.16 cm (4")
OD: 1.27 cm (0.5") ½ NPT Fitting
Weight: 1.8 kg (4 lb)
Specifications
Dew Point: -60 to 40°C (-76 to 104°F)
Relative Humidity: 0 to 95% RH (non-condensing) unit displays dew point or humidity, as well as temperature
Maximum Sensor Pressure Rating: 750 psi (51.7 bar)
Sensor Body Material: 304 SS
Maximum Operating Temperature: 200°C (392°F) (at 0% RH)
Mesh Filter Top: Stainless Steel
Single Output: 4 to 20 mA loop powered (relative humidity or dew point)
Dew Point Accuracy: ± 1.0°C from -20 to 40°C (-4 to 104°F); ± 3.0°C below -20°C (-4°F)
Relative Humidity Accuracy: ± 1% RH from 15 to 40°C (59 to 104°F), 0 to 90% RH (non-condensing); ± 2% RH below 15°C (59°F) or above 40°C (104°F)
Display: 2 line LCD
Resolution: 0.1
Power: 4 to 20 mA loop powered, 2-wire 24 Vdc (typical) 12 to 28 Vdc
Dimensions (Enclosure): 88.9 L x 63.5 W mm (3.5 x 2.5") Mounting Center: 78.7 mm (3.1")
Dimensions of Probe:
Length: 10.16 cm (4")
OD: 1.27 cm (0.5") ½ NPT Fitting
Weight: 1.8 kg (4 lb)