Skip to search Skip to main content Skip to navigation

1-800-663-4209 | Welcome to our new website, found an issue or bug? Please report it here

We noticed you are from . Visit your local site for regional offers and live support.

TXDIN70-Series-Tx

Dual DIN Rail Temperature Transmitter w/ Programmable Inputs

Models In Stock
  • Provides Two-Channel Transmitters or Signal Isolators (4 to 20 or 0 to 20 mA)
  • Programmable Input Types and Ranges with the Optional External Display (required to program unit- model number is TXDIN70-DISPLAY)
  • DIN Rail Mounted
  • Inputs are not isolated- Only use UNGROUNDED thermocouple sensors
TXDIN70-Series-Tx
From $ 214.89
Models In Stock
Dual DIN Rail Temperature Transmitter w/ Programmable Inputs TXDIN70-Series-Tx TXDIN70-Series-Tx
loading all models
Product Overview
  • Accuracy ± 0.3 %
  • Accuracy Detail Retransmission Accuracy: 0.3% full scale ±1 digit (including input and output error)
  • Approvals CE
  • Drift < 0.01 % FSO/°C
  • Electrical Output 0 to 22 mA
  • EMC Standard IEC 61000-4-4, IEC 61000-4-5
  • Height 100 mm
  • Length 100 mm
  • Mounting DIN Rail Mount
  • Number of Inputs 3
  • Operating Temperature, Max 60 °C
  • Operating Temperature, Min -10 °C
  • Output Detail Can be freely defined in the range of 0 to 22 mA with maximum output voltage ≥11V
  • Output Signal Current
  • Output Value Process
  • Power Consumption max 3 W
  • Relative Humidity ≤90% RH
  • Supply Power Type AC/DC
  • Weight 85 g
  • Width 22.5 mm
It provides 2 channels of configurable inputs, and supports multiple voltage, RTD, thermocouple inputs with auto reference junction compensation. If parallel connected to an external precise resistance, it accepts current signal input. Each channel has its own digital filtering and can adjust its filtering degree.
  • It generates two isolated current outputs, 4 to 20 or 0 to 20 mA. The range of retransmission output can be freely defined.
  • The model is DIN rail mounted. Its width is only 22.5 mm. The instrument can be easily configured by connecting to our E8 handset display.
  • Universal power supply of 100 to 240 Vac or 24 Vdc.
SPECIFICATIONS
Input Type
Thermocouple: K, J, T, E, R, S, B, N WRe5-WRe26
RTD: Pt100, Cu50
Linear Voltage: 0 to 20 mV, 0 to 60 mV, 0 to 100 mV, 0 to 1V, 0.2 to 1V
Instrument Input Range K(-50 to 1300°C), S(-50 to 1700°C), R(-50 to 1700°C), T(-200 to 350°C), E(0 to 1000°C), J(0 to 1200°C), B(0 to 1800°C), N(-50 to 1300°C), WRe5%WRe26(0 to 2300°C), Pt100(-200 to 900°C)
Linear Input: -9990 to 30,000 units defined by user
Retransmission Accuracy: 0.3% FS ± 1 digit (including input and output error)
Output Specification: Can be freely defined in the range of 0 to 22 mA with maximum output voltage ≠¥11V
Temperature Drift: ≠¥0.015%FS/°C (including the temperature drift of input and output)
Electromagnetic Compatibility (EMC): ± 4 KV/5 KHz according to IEC61000-4-4 (EFT); 4 KV according to IEC61000-4-5
Isolation Withstanding Voltage: Voltage between power, signal input and output terminals ≠¥2300 Vdc;
Power Supply: 100 to 240 Vac, -15%, +10% /50 to 60 Hz; or 24VDC
Power Consumption: ≠¥3W
Operating Ambient: Temperature -10 to 60°C; humidity ≠¥90%RH
Note: B thermocouple obtains the above measurement accuracy only at the range of 400 to 1800°C. It's measurement from 60 to 400°C is less accurate.
Read More

Accessories

External plug-in display (display is required to program transmitter). Display comes with cable
$72.02
156 In Stock
en-US
en
Save Configuration