1-800-663-4209 | Welcome to our new website, found an issue or bug? Please report it here
CCT-05-125/225
Economical DIN Rail Signal Conditioners
Choose a Variant
Input Type
Current Measurement Range
Voltage Measurement Range
Temperature Measurement Range
Product Specs
<< See all Product Models| Brand |
|
| Accuracy | ± 0.2 % |
| Approvals | CE, UL |
| Approvals Note | Enclosure: UL 94 V-1, Terminal Housing: UL 94-2 |
| Bandwidth | 1.5 Hz (-3 dB) |
| Current Measurement Range | N/A |
| Electrical Output | 4 to 20 mA |
| Enclosure Ratings | IP20, IP40 |
| Frequency Measurement Range | Min: 0 to 125 Hz, Max: 0 to 225 Hz |
| GrossWeightValue | 0 |
| Height | 75 mm |
| Input Type | Frequency |
| Isolation | 2000 Vrms |
| Length | 110 mm |
| Materials | Polycarbonate, RAL 7032 |
| Mounting | DIN Rail 46277 and EN 50022 |
| Number of Inputs | 1 |
| Operating Temperature, Max | 60 °C |
| Operating Temperature, Min | -10 °C |
| Output Detail | 4 to 20 mA and 0 to 10 Vdc standard; 0 to 20 mA via jumper select |
| Output Ripple | ≤0.5% |
| Output Signal | Current, Voltage |
| Output Value | Process |
| Power Consumption | max 1.5 VA |
| Response Time | ≤250 ms |
| Serial Number | Break Protection: Jumper selectable, upscale (>20 mA) or downscale (<4 mA) |
| Series ID | CCT-Series-Sig-Cond |
| Storage Temperature, Max | 80 °C |
| Storage Temperature, Min | -30 °C |
| Supply Power Note | 110 Vac (standard); 220 Vac or 24 Vdc (optional) (±10% tolerance on all power supplies) |
| Supply Power Type | AC |
| Supply Voltage | 110 Vac |
| Temperature Coefficient | ≤0.015%/°C |
| Temperature Measurement Range | N/A |
| Voltage Measurement Range | N/A |
| Voltage Output Range | 0 to 10 Vdc |
| Weight | 270 g |
| Width | 45 mm |
| Wire Gauge | 14 AWG |
| Country of Origin | Spain |
| See All Specs | |
PDFs & Manuals
Show Ratings & Reviews
Rated 5 out of
5
by
Russell from
turns Pt thermometer into 0-10V signal
The low level output of a Pt thermometer will result in a staircase graph when used with an analog to digital converter with low resolution. Amplifying the output smooth's the graph, and increases the resolution very nicely.
Date published: 2016-08-23
Rated 5 out of
5
by
nafm from
easy to calibrate to my application
Replaced a unit that served well for almost 15 years..
Date published: 2017-09-03
Rated 5 out of
5
by
Purchasing Agent from
As desribed
Product arrived in a timely manner and as decribed
Date published: 2023-07-27