1-800-663-4209 | Welcome to our new website, found an issue or bug? Please report it here

DRST-FR-Freq-Sig-Cond
DIN Rail Frequency Input Signal Conditioner | Configurable
Models In Stock
- Configurable with a standard PC and TXUN-KIT communications unit
- Pulse Calculator
- Frequency Generator
- Galvanic Isolation
DRST-FR-Freq-Sig-Cond
From
$
619.70
Models In Stock

Product Overview
- Approvals Note EMC:2014/30/EU, LVD:2014/35/EU
- Calibration Temperature, Max 28 °C
- Calibration Temperature, Min 20 °C
- Electrical Output 0 to 20 mA
- EMC Standard NAMUR NE 21
- Enclosure Ratings IP20
- Frequency Measurement Range 0 to 20 kHz
- Fuse Rating 400 mA SB / 250 Vac
- Height 109 mm
- Isolation 3750 Vac
- Length 130 mm
- Linearity Error < 0.1% of span
- Load Resistance Voltage Output : ≥ 500 kΩ, Current Output : ≤ 600 Ω
- Mounting DIN Rail 46277
- Noise Calibration >60 dB
- Operating Temperature, Max 60 °C
- Operating Temperature, Min -20 °C
- Optional Power Note 0 to 999 s
- Output Value Process
- Power Consumption 3.5 W, Internal - 3 W
- Relative Humidity <95% RH
- Screw Terminal Torque 0.5 Nm
- Signal Dynamics Output 16 bit
- Stability Load Stability: ≤0.01% of span/100 Ω
- Supply Power Type AC/DC
- Update Rate 20 ms
- Warm Up Time 1 min
- Weight 240 g
- Width 23.5 mm
Advanced Features
• The DRST-FR signal converter can be configured with OMSET software in a standard PC and the TXUN-KIT communications unit.
Application
• The f/I function performs frequency to current and voltage conversion.
• The f/f function can be used for pulse division or multiplication and as a buffer collecting fast pulse trains.
• A scale factor may be entered in all functions. Using both digital inputs, pulse addition or subtraction are possible.
• The frequency generator function is used as e.g. a time base or clock generator.
• Input and supply polarity reversal protection. Current and voltage output signals galvanically separated from the supply and the inputs.
• Programmable digital outputs including NPN, PNP or relay options.
Technical Characteristics
• 5 front LEDs, indicating f1 and f2 active inputs (not NPN), Dig.out.1 and 2 active outputs, and a programmable error signal.
• Analog current output can be configured to any current within 0 to 20 mA range.
• Voltage output range is selectable between 0 to 10 Vdc and 0 to 1 Vdc by use of internal jumpers.
• Input range: Frequency: 0 to 20,000 Hz Sensor types: NAMUR, tacho, NPN, PNP, TTL, S0
• Output range: Current and voltage output: 0 to 20 mA / 0...10 V Relay outputs: 0 to 20 Hz NPN and PNP output as f/f: 0 to 1000 Hz NPN and PNP output as generator: 0 to 20,000 Hz
• The DRST-FR signal converter can be configured with OMSET software in a standard PC and the TXUN-KIT communications unit.
Application
• The f/I function performs frequency to current and voltage conversion.
• The f/f function can be used for pulse division or multiplication and as a buffer collecting fast pulse trains.
• A scale factor may be entered in all functions. Using both digital inputs, pulse addition or subtraction are possible.
• The frequency generator function is used as e.g. a time base or clock generator.
• Input and supply polarity reversal protection. Current and voltage output signals galvanically separated from the supply and the inputs.
• Programmable digital outputs including NPN, PNP or relay options.
Technical Characteristics
• 5 front LEDs, indicating f1 and f2 active inputs (not NPN), Dig.out.1 and 2 active outputs, and a programmable error signal.
• Analog current output can be configured to any current within 0 to 20 mA range.
• Voltage output range is selectable between 0 to 10 Vdc and 0 to 1 Vdc by use of internal jumpers.
• Input range: Frequency: 0 to 20,000 Hz Sensor types: NAMUR, tacho, NPN, PNP, TTL, S0
• Output range: Current and voltage output: 0 to 20 mA / 0...10 V Relay outputs: 0 to 20 Hz NPN and PNP output as f/f: 0 to 1000 Hz NPN and PNP output as generator: 0 to 20,000 Hz
PDFs & Manuals
Accessories
accessories
Show Ratings & Reviews
Rated 5 out of
5
by
BT Hello from
Valuable Programmable Signal Converter
This product fits our use since it is stable and easy to use.
Date published: 2023-02-28
Is the TXUN-KIT require for setup?
Thank you for your question. The max input voltage from a tach is 80 VAC pp
Date published: 2023-11-17
Hi, What is the maximum Input Voltage signal ( From Tacho) it can handle? Thanks.
Thank you for your question. Max. input voltage......................... 80 VAC pp
Date published: 2023-12-11
is it possible to take one input signal and condition it into two outputs simultaneously? for example a analog output scaled from 0-5VDC and a conditioned square wave of 10Vpp that matches the input frequency? thank you in advance
Hello Joel
I'm sorry it does not have that capability, though what you can do is connect the output of the device to a DRSL-SP2 signal splitter and it can split it to two output signals.
Date published: 2020-04-03
Does this model have any shock test certification. other certification /approvals availble
Hello, thank you for your question. There are no certifications related to shock as we don't perform that kind of testing for signal conditioners.
Date published: 2024-05-28
regarding this type, do you have updated "EAC: TR-CU 020/2011" certificate?
Thank you for your question. You must send your question to:
Omega Engineering - Compliance
productcompliance@dwyeromega.com
Date published: 2025-08-11