DP6000
Models In Stock
DP6000
From
C$
1,161.90
Models In Stock
Product Overview
- Baud Rate 300 to 19200
- Calibration Calibrated at the factory. Recalibration is recommended at least every 12 months
- Category of Overvoltage II
- Category of Overvoltage Note Installation overvoltage category II; local level with smaller transient overvoltages than installation overvoltage category III
- Data Interface Modbus RTU
- Data Interface Note Protocol: Modbus RTU Meter Address/Slave ID: 1 – 247 Baud Rate: 300 to 19,200 bps Transmit Time Delay: Programmable between 0 and 199 ms Data: 8 bit (1 start bit, 1 or 2 stop bits) Parity: Even, odd, or none with 1 or 2 stop bits Byte-to-Byte Timeout: 0.01 to 2.54 seconds Turn Around Delay: Less than 2 ms (fixed)
- Digital I/O Note Channels: 4 digital inputs and 4 digital outputs per module System: Up to 2 modules for a total of 8 inputs and 8 outputs Digital Input Logic: High: 3 to 5 Vdc Low: 0 to 1.25 Vdc Digital Output Logic: High: 3.1 to 3.3 Vdc Low: 0 to 0.4 Vdc Source Current: 10 mA maximum Sink Current: 1.5 mA minimum +5 V Terminal: To be used as pull-up for digital inputs only
- Display Color Red
- Display Size 15 mm (0.60 in)
- Electrical Connection Screw Terminal
- Electrical Connection Note Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/o, and serial communication adaptors
- Enclosure Material Plastic
- Enclosure Ratings IP65, NEMA Type 4X
- Form factor 1/8 DIN
- Functions Noise Filter: Programmable from 2 to 199 (0 will disable filter) ;Filter Bypass: Programmable from 0.1 to 99.9% of calibrated span ;Cyber Security: 3 programmable passwords restrict modification of programmed settings; Pass 1: Allows use of function keys and digital inputs; Pass 2: Allows use of function keys, digital inputs and editing set/ reset points; Pass 3: Restricts all programming, function keys, and digital inputs
- Fuse Rating 5 A delayed
- Height 62 mm
- Input Type Note Input: Field selectable: 0 to 20 mA, 4 to 20 mA, ±10 Vdc (0 to 5, 1 to 5, 0 to 10V), MoDbuS PV (slave) Accuracy: ±0.03% of calibrated span ±1 count, square root and programmable exponent accuracy range: 10 to 100% of calibrated span Temperature Drift: 0.005% of calibrated span/°C max from 0 to 65°C ambient, 0.01% of calibrated span/°C max from -40 to 0°C ambient Signal Input Conditioning Function: Linear, square root, programmable exponent, or round horizontal tank volume calculation Multi-Point Linearization: 2 to 32 points for PV or PV1; 2 to 8 points for PV2 (dual-scale level feature) Programmable Exponent: 1.0001 to 2.9999 Low-Flow Cutoff: 0 to 999999 (0 disables cutoff function) Decimal Point: Up to 5 decimal places or none: d.ddddd, dd.dddd, ddd.ddd, dddd.dd, ddddd.d, or dddddd Calibration Range: 4 to 20 mA: Minimum span; input 1 and Input 2: 0.15 mA ±10 V: Minimum span; input 1 and 2: 0.10 V An Error message will appear if input 1 and input 2 signals are too close together Input Impedance: Voltage Ranges: Greater than 1 MΩ Current Ranges: 50 to 100 Ω (depending on resettable fuse impedance) Input Overload: Current input protected by resettable fuse, 30 Vdc max; fuse resets automatically after fault is removed
- Isolation 4 kV input/output-to-power line; 500 V input-to-output or output-to-P+ supply
- Length 143 mm
- Memory Non-Volatile Memory : All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost
- Mounting 1/8 DIN panel cutout required: 92 x 45 mm (3.622 x 1.772"); two panel mounting bracket assemblies are provided
- Normal Mode Rejection Greater than 60 db at 50/60 Hz
- Operating Temperature, Max 65 °C
- Operating Temperature, Min -40 °C
- Programmable Functions Filter Bypass, Noise Filter, Security
- Programming 4 front panel buttons, digital inputs, PC and software, Modbus registers, or cloning using copy function
- Relative Humidity 0 to 90% non-condensing
- Sampling Rate 5 Hz (5 updates/second)
- Series ID DP6000
- Storage Temperature, Max 85 °C
- Storage Temperature, Min -40 °C
- Supply Power Note 85 to 265 Vac 50/60 Hz, 90 to 265 Vdc, 20 W max, or jumper selectable 12/24 Vdc ±10%, 15 W max Isolated Transmitter Power Supply: 24 Vdc ±5% @ 200 mA max (standard), (12/24 Vdc powered models rated @ 100 mA max); 5 or 10 Vdc @ 50 mA max, selectable with internal jumper J4
- Tightening Torque Screw terminal connectors: 5 lb-in
- Weight 269 g
- Width 119 mm
- Wire Gauge 22 to 12 AWG