Skip to search Skip to main content Skip to navigation

Netherlands 07077 03815 | Intl +31 (0) 7077 03815 | Welcome to our new site - found a bug? Please report it here

We noticed you are in , please visit your local site by clicking the below link for regional offers and support.

TXUN-ST-FM-Series-Tx

2-Wire Programmable Transmitter with Universal Input

TXUN-ST-FM-Series-Tx
From  314,68
2-Wire Programmable Transmitter with Universal Input TXUN-ST-FM-Series-Tx TXUN-ST-FM-Series-Tx
loading all models
Product Overview
  • Accuracy ± 0.05 %
  • Accuracy Detail ≤ ±0.05% of span
  • ADC Resolution 20 bit
  • Approvals "Authority Requirements: EMC: 2014/30/EU RoHS: 2011/65/EU EAC: TR-CU 020/2011"
  • Cable Resistance 5 Ω
  • Calibration TXUN-KIT Communication Tool Kit
  • Calibration Temperature, Max 28 °C
  • Calibration Temperature, Min 20 °C
  • Cold Junction Compensation < ±1.0°C
  • DAC Resolution 16 bit
  • Diameter 44 mm
  • Drop 7.2 Vdc
  • Electrical Connection Screw Terminal
  • Electrical Output 4 to 20 mA
  • EMC Standard NAMUR NE 21
  • Enclosure Ratings IP00, IP68
  • Height 20.2 mm
  • Humidity Range Up to 95% non-condensing
  • Input Control Signal -12 to 800 mV
  • Input Resistance 10 MΩ
  • Input Type Thermocouple, RTD, Resistance, Voltage
  • Isolation 1500 V
  • Offset 50% of selected max. value
  • Operating Temperature, Max 85 °C
  • Operating Temperature, Min -40 °C
  • Output Detail Min. Signal Range: 16 mA NAMUR NE43 Upscale/Downscale: 23 mA/3.5 mA
  • Output Load  ≤ (Vsupply - 7.2)/0.023 Ω
  • Power Dissipation 25 mW to 0.8 W
  • Probe Length 0 mm
  • Programmable Functions Loop Link and HART
  • Response Time 1 to 60 sec
  • RTD Type Ni100,Pt100
  • Sensor Break Detection  3.5 to 23 mA
  • Sensor Current 0.2 mA
  • Sheath Material N/A
  • Signal/Noise Ratio > 60 dB
  • Stability ≤ 0.01% of span/100 Ω (Load Stability)
  • Supply Power Effects < 0.005% of span/Vdc
  • Supply Power Type DC
  • Supply Voltage 7.2 to 35 Vdc
  • Temperature Coefficient ≤ ±0.01%/°C
  • Temperature Input Range N/A
  • Thermocouple Type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
  • Update Rate, Max 440 ms
  • Vibration IEC 60068-2-6;2 to 25 Hz: ±1.6 mm;25 to 100 Hz: ±4 g
  • Warm Up Time 5 min
  • Weight 50 g
  • Wiring/Connector Table 2-, 3-, or 4-Wire

Application

• Linearized temperature measurement with Pt100...Pt1000, Ni100...Ni1000, or TC sensor.

• Conversion of linear resistance variation to a standard analog current signal, for instance from valves or Ohmic level sensors.
• Amplification of a bipolar mV signal to a standard 4 to 20 mA current signal.

Technical Characteristics
• Within a few seconds the user can program PR5331A to measure temperatures within all ranges defined by the norms.
• The RTD and resistance inputs have cable compensation for 2/3 and 4-wire connection.
• A continuous check of vital stored data for safety reasons.
en-NL
en_NL
Save Configuration