1-800-663-4209 | Welcome to our new website, found an issue or bug? Please report it here
RDA-Series
Low Cost Paperless Recorder with Color Touch Screen Display
Enregistreur sans papier à faible coût avec écran tactile couleur
Models In Stock
- Color TFT Touch Screen Display: 5'' or 7''
- 2, 4, or 6 Isolated Inputs for Thermocouple or RTD models
- 2 Internal Alarm setpoints per channel
- Maximum sample rate of 1 Hz
RDA-Series
From
C$
1,022.30
Models In Stock
Product Overview
- Accuracy ± 0.2% FS ± 1 digit
- Additional Features 1 USB Export
- Approvals EMC
- Cooling Natural Air Cooling
- Data Interface USB
- Display Note Color: TFT True Color, Resolution: 800 x 480, Backlit: Long-life LED, Input Method: Screen Touching, Touch Screen: Four-wire Resistive
- Display Resolution 800 x 480 Pixels
- Display Type LCD
- Enclosure Ratings Note EMC: 4KV/5KHz according to IEC61000-4-4 (Electrical Fast Transient); 4KV according to IEC61000-4-5 (Electrical Surge)
- Height 105 mm
- Isolation Among power, relay contact or signal terminals 2300VDC, Among isolated electroweak terminals 600V
- Length 100 mm
- Measurement Type Temperature
- Mounting Wall Mount
- Operating Temperature, Max 60 °C
- Operating Temperature, Min -10 °C
- Relative Humidity 90% RH
- Response Time ≤1.5 seconds
- Sampling Rate 1 Hz (1 update/second)
- Series ID RDA-Series
- Storage Temperature, Max 80 °C
- Storage Temperature, Min -20 °C
- Supply Power Note 100 to 240 Vac, -15%, +10% / 50 to 60 Hz,Power Consumption: ≤5W
- Supply Power Type AC
- Supply Voltage 100 to 240 Vac
- Thermal Effects ≤0.01% FS/°C
- Width 145 mm
La série RDA d'enregistreurs multicanaux sans papier à écran tactile pour thermocouples ou RTD est une gamme d'enregistreurs de données à écran tactile grand format à prix avantageux qui intègre la mesure, l'affichage, l'alarme et l'enregistrement des données dans un seul instrument mince. La série RDA est disponible en modèles à écran 5 pouces et 7 pouces. L'instrument est facile à installer et ne nécessite aucune IHM externe. Selon le modèle, la série RDA peut prendre en charge 2, 4 ou jusqu'à 6 canaux d'entrée avec un type d'entrée thermocouple ou RTD, offrant une précision de mesure de 0,2 % FS. Chaque canal peut avoir des spécifications d'entrée indépendantes, avec racine carrée, multiplication, addition et soustraction. Tous les canaux sont équipés de fonctions de réglage numérique et de filtre. La série RDA fournit des enregistrements de tendances en temps réel via un graphique de tendance ou un graphique à barres. L'historique et les enregistrements d'alarme peuvent être consultés dans l'enregistreur lui-même grâce à une mémoire interne de 150 Mo ou exportés vers un périphérique de stockage USB externe. Les modèles RDA-740 et RDA-760 ont une profondeur d'installation réduite de 40 mm pour une utilisation dans les espaces restreints.
PDFs & Manuals
Show Ratings & Reviews
Hello, I would like to know what happens when the memory of the chart recorder reaches the maximum (150 MB): does it stop recording or do it overwrite on historical data? If it overwrites, does it do it starting from the oldest data? Thanks
Hi Lale
Thank you for the inquiry. When memory is full the newest data will over write the oldest data.
Best regards
OMEGA
Date published: 2024-03-27
Does cold junction compensation require an external thermal resistor?
Hi Jimbo1831,
Thankyou for the inquiry. The cold junction compensation sensor is built in the RDA unit.
Best regards
OMEGA
Date published: 2021-10-27
Why does advanced function not allow me to enter 128 to create equation output? I can put in any number up to 128, but not the value required.
Hi Engineer6543,
Thank you for the inquiry. Please forward this question to TEMP@OMEGA.COM.
Best regards
OMEGA
Date published: 2022-08-26
How long does the internal memory last if recording 24hr a day?
Hi Steve,
The number of channels and the logging interval will impact the active logging period available. For 2 channels at 10 second interval you would have several months capacity.
Best regards
OMEGA
Date published: 2022-09-22
Is there a way to take a screenshot of the temperature plots?
Hi Rlied
Thank you for the inquiry. There is no screen capture function or video output feature unfortunately.
Best regards
OMEGA
Date published: 2021-08-26
My logger does not "store" any data. The History and the DataList tabs only start taking data once I go into that screen. If I exit back out to the Panel screen, any previous data is lost.
Hi TimRMC,
Thankyou for the inquiry. Please forward this question to TEMP@OMEGA.COM.
Best regards
OMEGA
Date published: 2022-10-04
Does the unit come with a power supply?
Thank you for your inquiry. This unit does not come a power supply. This unit requires 100 to 240 Volts AC Signal to be hard wired to it.
Date published: 2023-12-05
Can I use the "Sc" button to apply an offset to the thermocouples connected to the chart recorder? If so, does the "Sc" value correspond to the offset I want to apply? I have a RDA-760-TC
Hi Darvida,
Thank you for the inquiry. Sc is a display offset to correct for probe errors. But value for each count is 0.1 on the display count.
Best regards
OMEGA