Skip to search Skip to main content Skip to navigation

Taiwan 0809 090 375 | Intl +65 6415 5353 | Welcome to our new site - found a bug? Please report it here

We noticed you are in , please visit your local site by clicking the below link for regional offers and support.

LVCN210-Series

Ultrasonic Level Transmitter and Controller

Models In Stock
  • Level Detection, Switch and Control Functions Up to 3 m (9.8')
  • Fast and Easy Configuration Via Free Software Download and USB Adaptor
  • Narrow 5.08 cm (2') Beam Width and Short 10 cm (4') Dead Band
  • Four Programmable Relays
LVCN210-Series
From SGD 1,315.81
Models In Stock
Ultrasonic Level Transmitter and Controller LVCN210-Series LVCN210-Series
loading all models
Product Overview
  • Accuracy ± 0.2 %
  • Beam Width 2 in
  • Cable Length 48 in
  • Cable Type Insulated Shielded
  • Configuration Free PC Windows® USB 2.0.The level sensor is configurable via our free PC software and USB adaptor. The sensors are offered with and without USB connectors. Connectors can be used to configure many compatible level products. Download your free copy at
  • Contact Fail-Safe Power Loss: Hold Last
  • Data Interface USB
  • Diameter 3.06 in
  • Electrical Output 4 to 20 mA
  • Enclosure Ratings NEMA Type 13
  • Height 4.9 in
  • Insulation Polyurethane
  • Loop Resistance 400 Ω max
  • Materials FKM, Fluoroelastomer, Polycarbonate, Polyvinylidene, Fluoride
  • Mean Hysteresis Selectable
  • Measuring Range, Max 9.8 ft
  • Measuring Range, Min 0 ft
  • Media Compatibility Clean process / cooling water, Corrosive chemicals / acids / bases, Hydraulic fluids, Oils / lubricants, Organic solvents, Solvents, Water, Water-based fluids
  • Memory Non - Volatile
  • Number of Wires 2
  • Operating Pressure, Max 30 psi
  • Operating Temperature, Max 60 °C
  • Operating Temperature, Min -35 °C
  • Output Signal Current
  • Process Connection Size 1 in
  • Process Connection Type NPT Male
  • Process Temperature, Max 60 °C
  • Process Temperature, Min -7 °C
  • Resolution 0.039 in
  • Series ID LVCN210-Series
  • Signal fail-safe 4 mA, 20 mA, 21 mA, 22 mA or hold last
  • Signal invert 4 to 20 mA or 20 to 4 mA
  • Supply Voltage 24 Vdc
  • Switch Rating 60 VA,1A max
  • Switch Type SPST
  • Temperature Compensation Automatic

Supported Applications

The Omega LVCN210 Series is an ultrasonic level transmitter and controller designed for continuous measurement in small to medium tanks. As a non-contact sensor, it replaces float, conductance, and pressure sensors that may fail due to contact with dirty, sticking, or scaling media. The series supports general-purpose applications including day tank, skid, IBC, sump, machine, tool, and process tank level monitoring.

Operating Conditions & Performance

The LVCN210 Series provides a measurement range of 3 m (9.8') with an accuracy of ±0.2% of range and a resolution of 1 mm (0.039"). The sensor operates within a process temperature range of -7 to 60°C (20 to 140°F) and an ambient temperature range of -35 to 60°C (-31 to 140°F). It features automatic temperature compensation.

Performance specifications include a dead band of 10 cm (4") and a beam width of 5.08 cm (2"). The unit is rated for a Maximum Working Pressure (MWP) of 2 bar (30 psi). The enclosure carries a Type 6P rating, described as encapsulated, corrosion resistant, and submersible.

Configuration Options

The series offers configurable outputs, switching capabilities, and mounting options to accommodate specific installation needs. Key configuration parameters include:

  • Signal Output: 4 to 20 mA two-wire loop powered by 24 Vdc (loop). Signal invert is available as 4 to 20 mA or 20 to 4 mA.
  • Fail-Safe Logic: Configurable signal fail-safe options include 4 mA, 20 mA, 21 mA, 22 mA, or hold last. Contact fail-safe logic for power loss is set to Hold last; echo loss can be configured as Open, close, or hold last.
  • Relay Outputs: Four (4) SPST relays with a contact rating of 60 VA, 1A maximum. Hysteresis is selectable for the LVCN210 model.
  • Process Connection: Standard 1 NPT thread; optional 1" G thread available by adding "-G" to the model number.
  • Housing & Materials: Polycarbonate enclosure with a PVDF transducer. The mount gasket is FKM, and the cable jacket is Polyurethane (9-conductor, shielded).

The sensor includes non-volatile memory for configuration retention. Configuration is performed via free PC Windows® USB 2.0 software using an optional USB connector.

Key Product Differences

The LVCN210 Series distinguishes itself within the broader family by its specific range and output integration:

  • LVCN210: Includes a level transmitter with 4 to 20 mA signal, four relays, and an integrated USB connector for configuration.
  • LVCN210-B: Level transmitter with 4 to 20 mA signal and four relays; requires the separate LVCN414-USB accessory for software configuration.

The series is distinct from other family members (LVCN318, LVCN414) which offer different measurement ranges up to 5.5 m or alternative output signals such as voltage and frequency. The LVCN210 Series specifically targets the 3 m range with integrated relay control.

Accessories

cables

USB FOB / EOL SEE LVU500-USB
/ each
0 In Stock
This item is discontinued. Please contact Technical Sales Team for assistance.

installation hardware

1 NPT SIDE MOUNT BRACKET
TWD3,257 / each
0 In Stock
2 NPT X 1 NPT - SCH80
TWD2,473 / each
0 In Stock
en-TW
en_SG
Save Configuration