Models In Stock
  • Dual 4 digit green LCD display timer
  • 13 programmable timing modes
  • 9 time ranges from 99.99sec to 9999hrs
  • 1 changeover and 1 N/O relay output
PTC-13-A-Series
From C$ 463.12
Models In Stock
Programmable Dual Digital Timer, Universal Power PTC-13-A-Series PTC-13-A-Series
loading all models
Product Overview
  • Accuracy ± 0.01 %
  • Contact Rating OP1 10A at 250Vac/30Vdc (resistive);OP2 5A at 250Vac/30Vdc (resistive)
  • Control Output 2 SPDT Relay
  • Display Color Green
  • Display Type Dual 4 digit LCD
  • Enclosure Ratings IP20, IP65
  • Form factor 1/16 DIN
  • Frequency 50 to 60 Hz
  • Input Type Pulse
  • Operating Temperature, Max 50 °C
  • Operating Temperature, Min 0 °C
  • Output Configurations Open collector output, maximum 30Vdc, 100mA
  • Output Detail Single pole changeover contact and single pole N/O contact
  • Relay Rating Electrical: 200,000 operations;Mechanical: 5,000,000 operations
  • Series ID PTC-13-A-Series
  • Storage Temperature, Max 70 °C
  • Storage Temperature, Min -25 °C
  • Supply Power Note 90-250 Vac (±10%), Burden: < 5VA
  • Time Ranges 0.01 to 99.99sec,;0.1 to 999.9sec, 1 to 9999sec,;00:01 to 99:59min, 0.1 to 999.9min,;1 to 9999min, 00:01 to 99:59hrs,;0.1 to 999.9hrs, 1 to 9999hrs;
  • Weight 230 g

Supported Applications

The Omega PTC-13-A Series comprises multifunction digital timers designed for controlling equipment, machinery, systems, or processes in industrial applications. These programmable dual digital timers feature a two-line, four-digit display and support timing functions ranging from 0.01 seconds to 9999 hours.

Operating Conditions & Performance

The series operates within an ambient temperature range of 0°C to +50°C (32°F to 122°F) with storage capabilities between -25°C and +70°C (-13°F to 158°F). Relative humidity must not exceed 80% for temperatures up to 31°C, decreasing linearly to 50% relative humidity at 40°C. Installation height is limited to a maximum of 2000m.

Timing accuracy is specified as ±0.01% ±1ms. The device meets EN61010-1:2010 safety requirements (pollution degree 2, overvoltage category II) and satisfies performance criterion B for EN 61326-1:2013 EMC directives regarding EN 61000-4-3. The enclosure provides an IP65 rating on the front and IP20 on the rear.

Configuration Options

The series is available in two primary power supply configurations:

  • PTC-13-LV-A: 9-30Vdc/7-24Vac (±10%)
  • PTC-13-A: 90-250Vac 50/60Hz (±10%)

The timers offer extensive configuration options including nine selectable time ranges and thirteen different timing modes. Input signal types can be set to PNP or NPN in programming mode, with adjustable minimum pulse and void duration times between 5ms and 100ms.

Outputs and Connections

  • Relay Outputs: OUT1 provides a single pole changeover contact rated at 10A @ 250Vac (resistive load); OUT2 provides a single pole N/O contact rated at 5A @ 250Vac (resistive load).
  • SSR Outputs: Two open collector outputs (SSR1 & SSR2) with maximum ratings of 30Vdc and 100mA.
  • Auxiliary Power Supply: 12Vdc, maximum 50mA (un-regulated).

Data retention is handled via EEPROM with a minimum lifespan of 10 years. Electrical connections utilize plug-in terminals for signals and screw type terminals for power supply.

Mechanical Specifications

  • Housing: Self-extinguishing plastic case suitable for flush-panel mounting according to DIN 43700.
  • Dimensions: The series features a standard square size of approximately 48mm wide x 48mm high with depths ranging from 58.0mm to 87mm depending on the specific model documentation reference.
  • Weight: Approximately 230g (without packaging).

Key Product Differences

The primary distinction between models in this series is the power supply voltage. The PTC-13-LV-A model supports low-voltage AC and DC inputs, while the PTC-13-A model operates on universal mains voltage (90-250Vac). Both variants share identical timing modes, accuracy specifications, output configurations, and environmental ratings.

Users must observe specific warnings: do not use this timer in locations where corrosive or flammable gases could be present. When cleaning the unit, solvents such as thinners, gasoline, or acid must not be used to avoid invalidating the product guarantee.

Rated 5 out of 5 by from Timer Excellent unit we use for a timed washout system. It was easy to program and has been reliable.
Date published: 2024-04-23
  • y_2026, m_8, d_14, h_4
  • bvseo_bulk, prod_bvrr, vn_bulk_3.0.48
  • cp_1, bvpage1
  • co_hasreviews, tv_0, tr_1
  • loc_en_CA, sid_PTC-13-A, prod, sort_[SortEntry(order=HELPFULNESS, direction=DESCENDING), SortEntry(order=POSITIVE_FEEDBACK, direction=DESCENDING), SortEntry(order=SUBMISSION_TIME, direction=DESCENDING)]
  • clientName_omega
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 4ms
  • REVIEWS, PRODUCT

I have all four of the timed stages programed. However I want to run the program 3 times. I thought that the PTC-13-A had a cycles option. But I can not seem to isolate the option anywhere on page 5 nor in the timing modes listed pages 6-8. Am I being th

Asked by: Anonymous
Thank you for your inquiry. We believe the best assistance would come from speaking to us directly at 888-826-6342 ask for the Temperature Department Mon. &ndash; Fri. (HOURS 8:30AM - 5:00PM EST).
Answered by: Application Engineer CB
Date published: 2024-10-29
  • y_2026, m_8, d_13, h_8CST
  • bvseo_bulk, prod_bvqa, vn_bulk_3.0.48
  • cp_1, bvpage1
  • co_hasquestionsanswers, tq_1
  • loc_en_CA, sid_PTC-13-A, prod, sort_[SortEntry(order=NUM_ANSWERS, direction=DESCENDING)]
  • clientName_omega
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 23ms
  • QUESTIONS, PRODUCT
en-CA
en_CA
Save Configuration