Australia +61-2-4272 2055 | Welcome to our new website, found an issue or bug? Please report it here
CN76000-Series
1/16 DIN Universal Input Autotune Controller with Optional RS485
Models In Stock
- Dual 4-Digit Display
- Adaptive Tuning
- Autotune PID, PID, or On-Off Control
- Thermocouple Input with 1° or 0.1° Resolution
CN76000-Series
From
AUD
1,930.78
Models In Stock
Product Overview
- Accuracy ± 0.25 %FS + 1 digits
- Alarm Note 2 alarms operate the same relay; 3.0 A resistive 250 Vac; form A contact (SPST); field programmable for absolute (non-tracking) or deviation (tracking); can be set anywhere within the scaling of the controller; selectable inhibit and power interrupt; automatic/manual reset
- Common Mode Rejection 140 dB minimum at 60 Hz
- Control Characteristics Control Action: Reverse (heat) or direct (cool) action; selectable for single or dual setpoint models; Control Modes: Time-proportioning and proportional control modes; selectable preset tune, autotune or manual PID, P, PI or PD with reset anti-windup; Proportional Band : 6 to 5000°F or equivalent °C units; 6 to 9990 for voltage/current inputs; Integral Time : 0.1 to 99.9 minutes, or off ; Derivative Time: 0.01 to 99.99 minutes, or off ; Cycle Time: 2 to 80 s ; Approach Rate: Off to 99.99 min ; On-Off Control: Adjustable on-off differential 2° to full scale in 1° steps, 2 counts to full scale in 1-count steps (voltage/current inputs) ; Ramp and Soak: One ramp time and soak time each adjustable from 0 to 100 hours; end procedure can be set for HOLD or OFF
- Cutout Dimensions 45 x 45 mm
- Display Type 4 Digit LED
- Enclosure Ratings NEMA Type 12, NEMA Type 2, NEMA Type 3R
- Height 48 in
- Impedance Input 3 MΩ min, thermocouple; 200 µA, RTD current; 249 Ω, current; 5 kΩ, voltage
- Input Type Thermocouple, RTD, Voltage, Current
- Isolation Relay and SSR outputs are isolated; current, voltage and logic outputs must not share
- Length 125 in
- Memory Non-volatile; no batteries required
- Normal Mode Rejection 65 dB typical, 60 dB at 60 Hz
- Operating Humidity 0 to 90% RH, non-condensing
- Operating Temperature, Max 55 °C
- Operating Temperature, Min -10 °C
- Power Consumption 5 VA
- Protection Loop Break Protection: Error message is initiated on shorted sensor or open heater circuit; break time adjustable from off to 99 minutes; Loop Break Alarm: On alarm relay equipped units, unit can be programmed to alarm on loop break
- Sensor Break Protection De-energizes control outputs to protect system
- Series ID CN76000-Series
- Set Point Adjustment Selectable
- Stability Line Voltage Stability: ±0.05% over supply voltage range; Temperature Stability: 4 µV/°C (2.3 µV/°F) typical, 8 µV/°C (4.5 µV/°F) maximum
- Storage Temperature, Max 80 °C
- Storage Temperature, Min -40 °C
- Supply Power Type AC/DC
- Supply Voltage 100 to 240 Vac, 132 to 240 Vdc
- Weight 227 g
- Width 48 in
Supported Applications
The Omega CN76000 Series is a microprocessor-based, 1/16 DIN universal input autotune controller designed for industrial temperature and process control. The series supports economical control of heating, cooling, and heat/cool processes using thermocouple, RTD, voltage, or current inputs.
Operating Conditions & Performance
The CN76000 Series operates within an ambient temperature range of -4 to 55°C (-4 to 131°F). Humidity ratings are specified as 0 to 90% RH up to 40°C (104°F), non-condensing, and 10 to 50% at 55°C (131°F), non-condensing. The front panel carries a NEMA 2, 3R, and 12 rating for dust and splash resistance.
Accuracy is specified as ±0.25% span ±1 digit across the supported input types. Resolution options include 1°F/1°C or 0.1°F/0.1°C depending on the selected range. The series accepts a wide variety of thermocouple inputs (Types J, K, T, E, R, S, B, N, C, and PLII) and RTD elements including Pt100, Pt1000, Ni100, and Ni120. Process current ranges include 0 to 20 mA and 4 to 20 mA; process voltage inputs support 0 to 5 Vdc and 1 to 5 Vdc.
Input Ranges by Sensor Type
- Type J: -100 to 1600°F (1°F resolution) or -100 to 990°F (0.1°F resolution)
- Type K: -200 to 2500°F (1°F resolution) or -190 to 990°F (0.1°F resolution)
- Type T: -350 to 750°F (1°F resolution) or -190 to 750°F (0.1°F resolution)
- RTD Pt100: -328 to 1607°F (1°F resolution) or -190 to 990°F (0.1°F resolution)
Configuration Options
The series offers configurable output types, alarm configurations, and communication options via model suffixes.
Output Configurations
- Single Output Models: Relay/DC Pulse (CN76(*)30), DC Pulse/AC SSR (CN76(*)20), 0 to 20 mA (CN76(*)50), and 0 to 10 Vdc (CN76(*)60).
- Dual Output Models: Combinations include Relay/DC Pulse + Relay/DC Pulse, DC Pulse/AC SSR + DC Pulse/AC SSR, or analog outputs paired with a relay/pulse output.
Options and Accessories
- -PV: Scalable recorder; process variable output 0 to 10 Vdc.
- -485A:** RS-485 Serial Communication (Note: No CE rating for -485A option).
- DPP-4: 1/16 DIN panel punch accessory.
- CNQUENCHARC: Noise suppression kit for mechanical relay models driving AC contactors or solenoids.
Power Supply and Electrical Connection
The controller accepts 100 to 240 Vac, nom., +10% -15%, 50 to 400 Hz, single phase. DC power options include 132 to 240 Vdc, nom., +10% -20%. Electrical connections are made via convenient screw terminals.
Key Product Differences
The CN76000 Series distinguishes between standard units and alarm units. The model number guide indicates that specifying "0" denotes a standard unit, while "1" designates an alarm unit for additional cost. Outputs are logic jumper selectable; specific models allow selection between relay and DC pulse, or between DC pulse and AC SSR.
Storage temperature is rated from -40 to 80°C (-40 to 175°F). The device incorporates non-volatile memory and password protection features for configuration security. Voltage and current inputs are fully scalable with a maximum setting range of -1999 to 9999 counts.
PDFs & Manuals