Modèles en stock
  • Type J or K Thermocouple or 2, 3 or 4-Wire Pt100 RTD Input
  • Powered By the Host (Output) Current Signal Loop
  • Slimline 6 mm (0.24') Housing
  • High Accuracy
DRSL-TEMP-Sig-Cond
Depuis C$ 278.65
Modèles en stock
DIN Rail Temperature Loop Powered Signal Conditioner DRSL-TEMP-Sig-Cond DRSL-TEMP-Sig-Cond
loading all models
L'aperçu du produit
  • Approvals CE, UL, RoHS
  • Calibration Temperature, Max 28 °C
  • Calibration Temperature, Min 20 °C
  • Electrical Output 4 to 20 mA
  • EMC Immunity Note NAMUR NE 21, A Criterion, Burst: <±1% of span (span = selected input range)
  • EMC Standard NAMUR NE 21
  • Enclosure Ratings IP20
  • Height 113 mm
  • Installation Pollution degree 2 and measurement/overvoltage category II
  • Isolation 300 Vac
  • Length 115 mm
  • Load Resistance Resistance: ≤(Vsupply - 5.5)/0.023
  • Mounting DIN Rail 35 mm Standard, EN 60715
  • Noise Calibration >60 dB
  • Operating Temperature, Max 70 °C
  • Operating Temperature, Min -25 °C
  • Output Value Process
  • Power Consumption 0.7 W
  • Relative Humidity 0 to 95% RH (non-condensing)
  • RTD Accuracy ± 0.05 %
  • Screw Terminal Torque 0.5 Nm
  • Stability Load Stability: ≤0.01% of span/100 Ω
  • Storage Temperature, Max 85 °C
  • Storage Temperature, Min -40 °C
  • Supply Power Type DC
  • Voltage Loss 5.5 Vdc
  • Weight 70 g
  • Width 6.1 mm
  • Wire Gauge 26 to 12 AWG
The DRSL-TEMP isolated DIN rail loop-powered temperature signal conditioner measures a standard type J or K thermocouple or a 2-, 3- or 4-wire Pt100 RTD temperature sensor and provides a passive analog current output signal. The DRSL-TEMP offers 2-way isolation between input and output, provides surge suppression and protects control systems from transients and noise. The DRSL-TEMP provides a competitive choice in terms of both price and technology for interfacing thermocouple or RTD signals to SCADA systems or PLC equipment. This unit is powered by the host (output) current signal loop. Low power consumption facilitates DIN rail mounting without the need for any air gap. Easy configuration of more than 1000 factory calibrated measurement ranges is done via DIP-switches. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).

Accessories

installation hardware

Module stop (screwed onto DIN rail to support and hold mounted devices)
C$14.81
35 In Stock
35 mm DIN rail, 1 m (3.3 ft) length
C$29.45
16 In Stock
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getReviews, 4ms
  • REVIEWS, PRODUCT
  • bvseo-msg: The resource to the URL or file is currently unavailable.;

We have 10 DRSL-TC-ISOs to install. Can we use 2-wire RTDs as external cold junctions?

Asked by: Serge
Thank you for your question. Yes, 2 or 3-wire PT100 RTD is supported.
Answered by: PLENGR
Date published: 2024-08-14
  • y_2025, m_10, d_31, h_8CST
  • bvseo_bulk, prod_bvqa, vn_bulk_3.0.42
  • cp_1, bvpage1
  • co_hasquestionsanswers, tq_1
  • loc_en_CA, sid_DRSL-TEMP, prod, sort_[SortEntry(order=NUM_ANSWERS, direction=DESCENDING)]
  • clientName_omega
  • bvseo_sdk, java_sdk, bvseo-4.0.0
  • CLOUD, getContent, 11ms
  • QUESTIONS, PRODUCT
fr-CA
fr
Enregistrer la configuration