1-800-663-4209 | Bienvenue sur notre nouveau site Web, vous avez rencontré un problème ou un bug? Veuillez le signaler ici
 
								DRSL-DC1-DC2-Srs-Sig-Cond
DIN Rail Conditioner Series with Process Input, High accuracy
			Modèles en stock
	- Isolation and Conversion of Process Voltage or Current Signals
- Power Supply and Signal Isolator for 2-Wire Transmitter
- Slimline Housing—Only 6 mm (0.24') Wide
- Multiple Signal Ranges (DIP-Switch Selectable)
DRSL-DC1-DC2-Srs-Sig-Cond
					Depuis
					C$
					363.00
				
						Modèles en stock
				
			
		     
L'aperçu du produit
	- Précision ± 0.05 %
- Approvals CE, UL, RoHS
- Calibration Temperature, Max 28 °C
- Calibration Temperature, Min 20 °C
- Conversion Rate 1:1
- Current Measurement Range 0 to 20.5 mA
- Electrical Output 0 to 20.5 mA
- EMC Immunity Note Extended EMC Immunity NAMUR NE 21, A Criterion, Burst: <±1% of span
- EMC Standard NAMUR NE 21
- Enclosure Ratings IP20
- Height 113 mm
- Installation Pollution degree 2 and measurement/overvoltage category II
- Length 115 mm
- Load Resistance Current Output: 23 mA/600 Ω max
- Mounting DIN Rail 35 mm Standard, EN 60715
- MTBF 284 yrs
- Noise Calibration >60 dB
- Operating Temperature, Max 70 °C
- Operating Temperature, Min -25 °C
- Output Value Process
- Relative Humidity 0 to 95% RH (non-condensing)
- Response Time < 7 ms
- Response Time Note Response Time (0 to 90%, 100 to 10%): <7 ms
- Screw Terminal Torque 0.5 Nm
- Stability Load Stability: ≤0.01% of span/100 Ω
- Storage Temperature, Max 85 °C
- Storage Temperature, Min -40 °C
- Supply Power Type DC
- Supply Voltage 16.8 to 31.2 Vdc
- Temperature Coefficient <±0.01% of span/°C
- Weight 70 g
- Width 6.1 mm
- Wire Gauge 26 to 12 AWG
  The DRSL-DC2 isolated DIN rail signal conditioner provides a competitive choice in terms of both price and technology for galvanic isolation of process voltage or current signals to SCADA systems or PLC equipment. The DRSL-DC2 can be used for signal conversion of standard process voltage or current signals. The unit offers isolation between input, output and supply, provides surge suppression and protects control systems from transients and noise.
The DRSL-DC2 also eliminates ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Factory calibrated measurement ranges are easily configured via DIP switches. When the input is configured for 2-wire transmitter mode, the DRSL-DC2 provides the current loop supply voltage. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).
The DRSL-DC2 also eliminates ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Factory calibrated measurement ranges are easily configured via DIP switches. When the input is configured for 2-wire transmitter mode, the DRSL-DC2 provides the current loop supply voltage. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).
				PDF et manuels
			
		Accessories
installation hardware
Module stop (screwed onto DIN rail to support and hold mounted devices)
					
					C$14.81
                      35 In Stock
                        Power rail (with cover and two end covers, one right hand and one le ft hand), 1 m (3.3 ft) length
					
					C$301.98
                      4 In Stock
                        meters/controllers
Afficher les notes et les avis
 
			
	
	
	
Would this work for high speed pulses coming from an encoder?
            Thank you for your inquiry. No, it does not support high speed pulses from an encoder. It will only accept dc voltage or current inputs only.
            
            
    Date published: 2023-12-11
         
						
						 
					
				