Galvanic Barrier, DIN Rail Mount, Plug-In, for Dwyer® Hazardous Areas
			Models In Stock
	- Easy snap-in installation for most DIN rails
 - Safe to use in hazardous locations
 
Series-MTL5541
					From
					C$
					1,670.59
				
						Models In Stock
				
			
		    Product Overview
	- Accuracy ± 15 µA
 - Applications Fluid Measurement and Control, Industrial and Manufacturing
 - Current Sink, Max 600 Ω max
 - Electrical Safety Vo= 28 V Io= 93 mA Po= 651mW Um= 253 RMS or DC. Weight: 5.3 oz (150 g)
 - Input Control Signal 16.2 Vdc
 - Isolation 250 V RMS, tested at 1500 V RMS minimum, between safe-area and hazardous-area terminals; 50 V between safe-area circuits and power supply
 - LED Indicators Green: Power indication
 - Load Resistance 0 to 360Ω @ 24 mA / 0 to 450Ω @ 20 mA
 - Mounting T-section 35 mm DIN rail to EN 50022
 - Operating Temperature, Max 140 °F
 - Operating Temperature, Min -6 °F
 - Output Detail Signal range: 4-20 mA; Under/over-range: 0-24 mA
 - Output Resistance >1 MΩ
 - Output Signal Current
 - Power Consumption 1 W
 - Relative Humidity 5 to 95% RH
 - Response Time 50 µs
 - Response Time Note Settles to within 10% of final value within 50 µs
 - Storage Temperature, Max 176 °F
 - Storage Temperature, Min -40 °F
 - Supply Power Type DC
 - Supply Voltage 20 to 35 Vdc
 - Temperature Drift < 0.8µA/°C
 - Terminal block up to 2.5 mm²
 - Weight 5.3 oz
 
The Series MTL5541 Galvanic Barrier provides intrinsically safe isolation for communication with Dwyer® transmitters approved for use in hazardous areas. This galvanic barrier eliminates the need for a high integrity earth ground required when using shunt type diode type safety barriers. DIN rail mounting and plug-in signal and power connectors simplify installation and maintenance.
Product Applications
- Electrically isolates pressure and level transmitters from unregulated circuits for intrinsically safe applications
 